3 Operation
(continued)
C232-302-401/402/403/404-603 / C232/EN M/A23
3-91
Fault data acquisition
The fault must last for at least 60 ms so that the fault data can be determined.
The fault data are determined using the maximum phase current and the geometric sum
of the three phase currents.
Fault current and ground fault current are displayed as per-unit quantities referred to
I
nom
. If the measured or calculated values are outside the acceptable measuring range,
the ‘
Overflow
’ indication is displayed.
22Z5119A
3-68
Acquisition of fault data (short-circuit data)
www
. ElectricalPartManuals
. com