Application Description
KNX-IMPZ2 2 Channel Impulse Counter
Page 8
3 KNX Objects
3.1 Objects - 2 Independent Counter
3.1. Objects - 2 Independent Counter
8
3.2. Objects - 1 Counter with 2 Scales
10
Objects - 2 Independent Counter - KNX-IMPZ2
No. Name
Data Point Type
Function
0
Meter reading channel 1
DPT
14.*
4 Byte
Meter reading
1
Meter reading channel 2
DPT
14.*
4 Byte
Meter reading
2
Capacity / Volumetric flow channel 1
DPT
14.*
4 Byte
Calculated flow
3
Capacity / Volumetric flow channel 2
DPT
14.*
4 Byte
Calculated flow
4
Reference value channel 1
DPT
14.*
4 Byte
Consumption for
the last reference
date
5
Reference value channel 2
DPT
14.*
4 Byte
Consumption for
the last reference
date
6
Consumption value channel 1
DPT
14.*
4 Byte
consumption
value
7
Consumption value channel 2
DPT
14.*
4 Byte
consumption
value
8
Serial number channel 1
DPT
16.000 String(ASCII)
14 Byte
Serial number
9
Serial number channel 2
DPT
16.000 String(ASCII)
14 Byte
Serial number
10
Limit alarm channel 1
DPT
1.001 Switch
1 Bit
Limit
11
Limit alarm channel 2
DPT
1.001 Switch
1 Bit
Limit
12
Current time
DPT
10.001 time
3 Byte
time
13
Current date
DPT
11.001 date
3 Byte
date
14
Last reference date
DPT
11.001 date
3 Byte
Reference date
15
Next reference date
DPT
11.001 date
3 Byte
Reference date
16
Consumption reset
DPT
7.001 Pulse
2 Byte
Consumption
value reset
17
Consumption reset time
DPT
10.001 time
3 Byte
Reset time
18
Consumption reset date
DPT
11.001 date
3 Byte
Reset date
19
Alarm Profile
DPT
1.001 Switch
1 Bit
Select time