Table. 5.5.8 - 279. Event messages.
Event block name
Event names
VJP1
Block ON
VJP1
Block OFF
VJP1
Trip ON
VJP1
Trip OFF
VJP1
Alarm ON
VJP1
Alarm OFF
The function registers its operation into the last twelve (12) time-stamped registers. The register of the
function records the ON event process data for START, TRIP or BLOCKED. The table below
presents the structure of the function's register content.
Table. 5.5.8 - 280. Register content.
Date and time
Event
Fault type
Trip Δα meas /
dataset
Alarm Δα meas /
dataset
Used SG
dd.mm.yyyy
hh:mm:ss.mss
Event
name
L1(2), L2(3), L3(1)
and U4
Trip angle difference Alarm angle
difference
Setting group 1...8
active
5.5.9 Synchronizer (ΔV/Δa/Δf; 25)
The synchronizer function is used to automatically synchronize generators to power grids. Proper
synchronizing is essential to avoid inrush currents, power system oscillations as well as thermal and
mechanical stress on the generator when connecting a synchronous generator to a grid.
The user can synchronize up to eight (8) circuit breakers with the same synchronizing function by using
different setting groups and the logic editor. The synchrocheck function is used to parallel or energize
power lines.
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00001
351