Table. 5.5.6 - 268. Hardware indications.
Name
Range
Step
Description
Hardware in mA output
channels 1...4
0: None
1: Slot A
2: Slot B
3: Slot C
4: Slot D
5: Slot E
6: Slot F
7: Slot G
8: Slot H
9: Slot I
10: Slot J
11: Slot K
12: Slot L
13: Slot M
14: Slot N
15: Too many cards
installed
-
Indicates the option card slot where the mA output card
is located.
Hardware in mA output
channels 5...8
Table. 5.5.6 - 269. Measurement values reported by mA output cards.
Name
Range
Step
Description
mA in Channel 1
0.0000…24.0000mA 0.0001mA Displays the measured mA value of the selected input
channel.
mA in Channel 2
mA Out Channel Input
Magnitude now
-10
7
…10
7
0.001
Displays the input value of the selected mA output
channel at that moment.
mA Out Channel Outputs
now
0.0000…24.0000mA 0.0001mA Displays the output value of the selected mA output
channel at that moment.
5.5.7 Synchronizer (ΔV/Δa/Δf; 25)
The synchronizer function is used to automatically synchronize generators to power grids. Proper
synchronizing is essential to avoid inrush currents, power system oscillations as well as thermal and
mechanical stress on the generator when connecting a synchronous generator to a grid.
The user can synchronize up to eight (8) circuit breakers with the same synchronizing function by using
different setting groups and the logic editor. The synchrocheck function is used to parallel or energize
power lines.
Genera
Generattor Commander
or Commander
Instruction manual
Version: 2.07
© Arcteq Relays Ltd
IM00001
341