Overloading
0: Not
active
1:
Active
-
0: Not
active
The
Ov
Overloading
erloading signal is active when the measured current exceeds the motor's
nominal current (including the ambient and service factor corrections) but does not
exceed the "Max overload current" setting.
High
overcurrent
0: Not
active
1:
Active
-
0: Not
active
The
Hig
High o
h ovver
ercurr
current
ent signal is active when the measured current is above the "Max
locked rotor current" setting and presents a situation where the motor cannot start
or stall. When this signal activates, it indicates a short-circuit fault and should
immediately be used to halt start-up or stalled situations.
Events and registers
The motor status monitoring function (abbreviated "MST" in event block names) generates events from
the detected motor status. The data register is available, based on the events.
Table. 5.3.17 - 155. Event messages.
Event block name
Event names
MST1
Motor Stopped OFF
MST1
Motor Starting ON
MST1
Motor Starting OFF
MST1
Motor Running ON
MST1
Motor Running OFF
MST1
Motor Stalled ON
MST1
Motor Stalled OFF
MST1
Load not symm ON
MST1
Load not symm OFF
MST1
Load normal ON
MST1
Load normal OFF
MST1
Overload ON
MST1
Overload OFF
MST1
High Overcurrent ON
MST1
High Overcurrent OFF
The function registers its operation into the last twelve (12) time-stamped registers. The table below
presents the structure of the function's register content.
Table. 5.3.17 - 156. Register content.
Date and time
Event
L1 current
L2 current
L3 current
Thermal delta
Motor load
dd.mm.yyyy
hh:mm:ss.mss
Event
name
Phase L1
current x I
n
Phase L2
current x I
n
Phase L3
current x I
n
Detected change in
thermal capacity.
Motor loading when
triggered.
5.3.18 Motor start/ locked rotor monitoring (Ist>; 48/14)
The motor start/locked rotor monitoring function is used for monitoring the start-up's duration as well as
the start-up's stress on the motor. The function can also be used after starting locked rotor protection.
A
AQ
Q-M255
-M255
Instruction manual
Version: 2.06
186
© Arcteq Relays Ltd
IM00020
Содержание AQ-M255
Страница 1: ...AQ M255 Motor protection IED Instruction manual...
Страница 2: ......
Страница 384: ...Figure 7 4 189 Example block scheme A AQ Q M255 M255 Instruction manual Version 2 06 382 Arcteq Relays Ltd IM00020...
Страница 405: ...Figure 8 14 211 Device installation A AQ Q M255 M255 Instruction manual Version 2 06 Arcteq Relays Ltd IM00020 403...