Signal
Range
Description
IndicatorX
Close
input
("Ind.X
Close
Status
In")
Digital input or other
logical signal selected
by the user
(SWx)
A link to a physical digital input. The monitored indicator's CLOSE status. "1" refers to
the active "Close" state of the monitored indicator. If IEC 61850 is enabled, GOOSE
signals can be used for status indication.
Events
The indicator object monitoring function (abbreviated "CIN" in event block names) generates events
from the status changes in the monitored signals, including the continuous status indications. The user
can select which event messages are stored in the main event buffer: ON, OFF, or both.
Table. 5.4.3 - 210. Event codes (instances 1 – 5).
Event Number
Event channel
Event block name
Event Code
Description
6656
104
CIN1
0
Intermediate
6657
104
CIN1
1
Open
6658
104
CIN1
2
Close
6659
104
CIN1
3
Bad
6720
105
CIN2
0
Intermediate
6721
105
CIN2
1
Open
6722
105
CIN2
2
Close
6723
105
CIN2
3
Bad
6784
106
CIN3
0
Intermediate
6785
106
CIN3
1
Open
6786
106
CIN3
2
Close
6787
106
CIN3
3
Bad
6848
107
CIN4
0
Intermediate
6849
107
CIN4
1
Open
6850
107
CIN4
2
Close
6851
107
CIN4
3
Bad
6912
108
CIN5
0
Intermediate
6913
108
CIN5
1
Open
6914
108
CIN5
2
Close
6915
108
CIN5
3
Bad
5.4.4 Synchrocheck (ΔV/Δa/Δf; 25)
Checking the synchronization is important to ensure the safe closing of the circuit breaker between two
systems. Closing the circuit breaker when the systems are not synchronized can cause several
problems such as current surges which damage the interconnecting elements. The synchrocheck
function has three stages: SYN1, SYN2 and SYN3. Their function and availability of these
stages depend on which voltage channels are set to "SS" mode or not. Voltage measurement settings
are located at
Measurements
→
Transformers
→
VT module.
A
AQ
Q-G215
-G215
Instruction manual
Version: 2.04
311
Содержание AQ-G215
Страница 1: ...AQ G215 Generator protection IED Instruction manual ...
Страница 399: ...Figure 7 4 241 Example block scheme A AQ Q G215 G215 Instruction manual Version 2 04 398 ...
Страница 421: ...Figure 8 14 264 Panel cutout dimensions and device spacing A AQ Q G215 G215 Instruction manual Version 2 04 420 ...
Страница 456: ...10 Ordering information A AQ Q G215 G215 Instruction manual Version 2 04 455 ...