5.3.15 Power protection (P, Q, S>/<; 32)
The power protection function is for instant and time-delayed, three-phase overpower or underpower
protection (active, reactive, or apparent). The user can select the operating mode with parameter
settings.
The figure below presents the pick-up areas of the function's different modes, displayed in a PQ
diagram.
Figure. 5.3.15 - 137. PQ diagram of the pick-up areas in various modes.
The outputs of the function are the START, TRIP and BLOCKED signals. The power protection function
uses a total of eight (8) separate setting groups which can be selected from one common source.
The function can operate on instant or time-delayed mode.
The operational logic consists of the following:
• input magnitude selection
• input magnitude processing
• threshold comparator
• two block signal checks
• time delay characteristics
• output processing.
The inputs for the function are the following:
• operating mode selections
• setting parameters
• digital inputs and logic signals
• measured and pre-processed power magnitudes.