Figure. 4.4 - 8. DIP switch diagram.
Table. 4.4 - 4. DIP switch settings.
PPin number
in number
((name
name))
FFunction selection
unction selection
ON (le
ON (left position)
ft position)
OFF (
OFF (rig
right position)
ht position)
8
(L> or
or L> + I>)
The tripping criterion for the S2,
S3, S4 (sensor) and S5 (fiber)
channels.
Tripping on light only (L>).
Tripping on light and overcurrent
(L> + I>), both of which are
required to occur simultaneously
to trigger tripping.
7
(S1: L> or
or L> +
I>)
The tripping criterion for the S1
sensor channel.
Tripping on light only (L>).
Tripping on light and overcurrent
(L> + I>), both of which are
required to occur simultaneously
to trigger tripping.
6
(Latch or
or Non-
latch)
Latching or non-latching for the
T1 and T2 trip relays.
T1 and T2 operate as latched.
T1 and T2 operate as non-
latched.
5
(100 ms or
or 150
ms)
The setting for the CBFP time.
The CBFP time is set to 100 ms.
The CBFP time is set to 150 ms.
4
(scheme select)
Scheme selection.
Please refer to the "Scheme
selection" and "Application
examples" chapters.
Please refer to the "Scheme
selection" and "Application
examples" chapters.
3
(scheme select)
Scheme selection.
Please refer to the "Scheme
selection" and "Application
examples" chapters.
Please refer to the "Scheme
selection" and "Application
examples" chapters.
2
(scheme select)
Scheme selection.
Please refer to the "Scheme
selection" and "Application
examples" chapters.
Please refer to the "Scheme
selection" and "Application
examples" chapters.
1
(scheme select)
Scheme selection.
Please refer to the "Scheme
selection" and "Application
examples" chapters.
Please refer to the "Scheme
selection" and "Application
examples" chapters.
A
AQ
Q-101 (A
-101 (AQ
Q-101D
-101D))
Instruction manual
Version: 2.01
© Arcteq Relays Ltd
IM00006
17