INSTALLATION INSTRUCTIONS

Modular Blower: MB

442 01 2405 01

3

Specifications subject to change without notice.

Figure 2

Attach Coil to Blower Cabinet

Panels

removed

for clarity only

Place seal

on top of

Coil Cabinet

around

perimeter

Bend Tabs (both sides

and back) on Bottom of

Blower Cabinet to Fit

over Coil Cabinet

Figure 3

Upflow/Downflow Airflow Positions

NON-DUCTED RETURN  AIR CLOSET

INSTALLATION

The cabinet can be installed in a closet with a false bottom to form a

return air plenum, or mounted on an open platform inside the closet.

Platform should be high enough to provide a free (open) area  for

adequate return airflow into the bottom of the cabinet. The open area

can be on the front side or a combination of front and sides, providing

there is clearance on the sides between cabinet and closet.

 Refer to

ACCA Manual D for sizing and free area recommendations.

NOTE:  

Local codes may limit application of systems without a ducted

return to single story dwellings.

HORIZONTAL LEFT AND RIGHT

INSTALLATIONS

The modular blower cabinets can be installed in either downflow, horizontal left, or
horizontal right applications. When a coil cabinet is applied, refer to the coil installation
manual for proper drain pan and airflow requirements. They must have the drain pan
repositioned for right hand airflow. Refer to coil installation manual.

!

CAUTION

PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property

damage.
A field fabricated auxiliary drain pan, with a separate

drain is REQUIRED for all installations over  a finished

living space or in any area that may be damaged by

overflow from a restricted main drain pan. In some loca-

lities, local codes require an auxiliary drain pan for ANY

horizontal installation.

Figure 4

Horizontal Airflow Positions

SUSPENDED  CABINET INSTALLATION

1. The cabinet may be supported on a frame or shelf, or it may be

suspended.

2. Use metal strapping or threaded rod with angle iron supports

under the auxiliary drain pan to suspend cabinet. These

supports 

MUST

 run parallel with the length of the cabinet

(

Figure 5 

).

3. Ensure that there is adequate room to remove service and

access panels after installing supporting brackets.

4. Place field installed vibration isolators in auxiliary drain pan to

support cabinet.

DUCT CONNECTIONS

Supply Duct

Supply duct must be attached to the outside of flange on outlet end of

unit. Flexible connectors may be used if desired.

Return Duct

Return duct should be attached to bottom of unit using sheet metal

screws or other fasteners.

FILTER INSTALLATION

Filters must be field supplied.  A remote filter grille or other means

must be provided. Refer to ACCA Manual D for remote filter sizing.

Содержание MB08B1500B

Страница 1: ... of the National Electrical Code NEC NFPA 70 In Canada refer to the current editions of the Canadian Electrical Code CSA C22 1 Recognize safety information This is the safety alert symbol When you see this symbol on the unit and in instructions or manuals be alert to the potential for personal injury Understand these signal words DANGER WARNING and CAUTION These words are used with the safety aler...

Страница 2: ...rt space in the front of the unit for service access clearance for return air and supply duct connections space for refrigerant piping connections and condensate drain line connections THESE BLOWERS ARE NOT TO BE USED WITH ELECTRIC HEAT If the unit is located in an area of high humidity nuisance sweating of casing may occur On these installations a wrap of 2 51mm fiberglass insulation with a vapor...

Страница 3: ...ments They must have the drain pan repositioned for right hand airflow Refer to coil installation manual CAUTION PROPERTY DAMAGE HAZARD Failure to follow this caution may result in property damage A field fabricated auxiliary drain pan with a separate drain is REQUIRED for all installations over a finished living space or in any area that may be damaged by overflow from a restricted main drain pan...

Страница 4: ...NT PROTECTION The power supply wiring to the unit MUST be provided with overcurrent protection Governing codes may require this to be fuses ONLY or circuit breakers For blower cabinets MB08 MB12 and MB16 a 15 AMP circuit should be used For MB20 a 20 AMP circuit should be used LINE VOLTAGE CONNECTIONS Line voltage wiring may be brought into the unit through the top right hand corner A hole for a 1 ...

Страница 5: ...pitot tubes or other accurate pressure sensing devices 3 Connect these taps to a level inclined manometer or draft gauge 4 Ensure the coil and filter are clean and all the registers are open 5 Determine the external static pressure with the blower operating 6 Refer to the Air Flow Data tables to find the speed tap that will most closely provide the required air flow for the system 7 Refer to Motor...

Страница 6: ...PPER 1 1 1 1 1176316 11 B6001801 BACK WRAPPER 1 1176312 B6001802 1 1176313 B6001803 1 1176314 B6001804 1 1176315 12 B60020 R H SIDE WRAPPER 1 1 1 1 1176317 Replacement Parts Expanded View B50086B KEY NO PART NUMBER DESCRIPTION MB08B1500B2 MB12F1900B2 MB16J2200B2 MB20L2400B2 OLD PART 13 B6003601 BRACE BOTTOM FRONT 1 1069603 B6003602 1 1069604 B6003603 1 1069605 B6003604 1 1087670 14 B6005601 DECK B...

Отзывы: