2.1.3 LENGTH OF FLUE GAS DUCT:
PIXEL 31 FC
2.1.3.1 SPLIT FLUE
Ø 80 mm
N.B.: The flue and aspiration
duct lenght has not to exceed
30 m.
By 0 to 2 m you must put
a Ø 42 mm diaphragme in
the outlet of the fan.
For every added 90° elbow the
maximum allovable lenght is to
be diminuished by 2 m.
The pipes of aspiration and unloading
must be climbed on upward with
inclination of 3° so that the
condensing product flows into the
boiler rather than to the outside.
2.1.3.2 COAXIAL
FLUE
Ø 60 x 100 mm
N.B.: The allowed lenght
of coaxial flue ducts is by
a minimum 0,5 meters to
a maximum of 4 meters.
By 0 to 2 m you must put
a Ø 42 mm diaphragme
in the outlet of the fan.
The ducts must be
climbed on with light
inclination toward the
outside.
The pipes of aspiration and unloading
must be climbed on upward with
inclination of 3° so that the
condensing product flows into the
boiler rather than to the outside.
11
175
MAX 15 m +
MAX 15 m
105 120
STRAIGHT ON
MAX 15 m
MAX 4 m
143
171
314
MAX 4 m
100