NOsparc MGXDC1F250 USER MANUAL

 

Ÿ

 

Page 5 of 6 

 

www.ArcSuppressionTechnologies.com 

 

Arc Suppression Technologies 

 

SPECIFICATIONS 

CONTACT Specifications 

ABSOLUTE MAXIMUM CURRENT 

RATING 

75A – This absolute maximum current rating also represents the maximum allowable Locked Rotor Amperage 

(LRA) for motor loads and the cold filament inrush current for tungsten loads 

ARC SUPPRESSION 

duration: 1ms (typical) 

CIRCUITS  

(CONTACTS)

 

one (1) NOsparc per contact (multiple NOsparc units required for multi-contact relays) 

CIRCUIT BREAKER / FUSE 

(MAXIMUM)

 

50A for resistive loads (see Safe Operating Area charts below for more detail) 

CLAMPING VOLTAGE  

330V (typical at 1 mA) 

CYCLING 

maximum cycle time: per relay specifications (DO NOT EXCEED relay or contactor operating specs) 

LEAKAGE CURRENT 

0.5mA (nominal) 

OPERATING VOLTAGE  

12Vdc to 250Vdc 

TERMINATION 

across contacts: two (2) 0.250” insulated quick connect terminals 

GENERAL Specifications 

DIMENSIONS 

length:  2.380in (6.045cm) x width:  1.070in (2.718cm) x height:  0.740in (1.880cm) 

ENVIRONMENTAL 

operating temperature:  -40°C  to 85°C  (-40°F to 185°F),  storage temperature:  -50°C to 125°C (-58°F to 257°F), 

humidity:  5% to 95% (non-condensing) 

MOUNTING 

orientation: any           number of holes: two (2)           hole diameter: 0.150in (#6 screw) (3.81mm) 

MTBF / RELIABILITY 

800,000 hours (MIL-HDBK-217F) 

POWER-ON 

load current passthrough:  1ms 

POWER TYPE 

DC (direct current) 

WEIGHT 

1oz (28g) 

WIRE GAUGE 

wire length between NOsparc and contact terminals: 0in to 24in:  #14AWG (minimum); 24in to 36in:  #12AWG (minimum) 

NOTE: DO NOT use wire lengths over 3 feet 

 

 

CIRCUIT BREAKER / CIRCUIT FUSE DE-RATINGS 

The chart (right) depicts the circuit breaker / circuit fuse Safe Operating Area (SOA) for different loads. 

 

 

 