IRIG-B Information
IRIG Time Code Formats
Listed below are the various formats in the IRIG specification.
Arbiter clock products produce Format B.
Format
Pulse Rate
Index Count
Interval
IRIG-A
1000 PPS
1 ms
IRIG-B
100 PPS
10 ms
IRIG-D
1 PPM
1 minute
IRIG-E
10 PPS
100 ms
IRIG-G
10000 PPS
0.1 ms
IRIG-H
1 PPS
1 second
Table 2: Various IRIG Time Code Formats
Time Code Attributes
All IRIG time code formats use pulse-width coding. A ”binary
1” pulse has a duration of 50% of the index count interval (see
Table 2); a ”binary 0” pulse has a duration of 20% of the index
count interval; pulse identifiers have a duration of 80% and used
as reference markers.
IRIG-B time code signals may be either Unmodulated or Mod-
ulated. Unmodulated time codes are DC level shift with no carrier
signal. Modulated time codes are amplitude-modulated, sine wave
carrier. For IRIG-B, the carrier is 1 kHz.