Power
” sets the Model 931A to calculate active power (watts).
Based on voltage and current measurements from the predefined
inputs, the results are compared to an active power transducer. For
three-phase configurations, the display shows total active power. See
Section 3.6.2 for a description of power measurements.
“
Volt-Amps
” sets the Model 931A to calculate apparent power
(VA). Based on voltage and current measurements from the pre-
defined inputs, the results are compared to an apparent power
transducer. For three-phase configurations, the display shows the
total apparent power. See Section 3.6.3 for a description of apparent
power measurements.
“
Amps
” sets the Model 931A to make current measurements on the
predefined input routed to Channel 2 and compares it to a current
transducer. Route input to measurement Channels 1 and 2 if only a
current signal is available.
If available, route synchronous voltage signal to channel 1.
For
three-phase configurations, the display shows average current. See
Section 3.2.3 for a description of AC current measurements.
“
Frequency
” sets the Model 931A to measure frequency at (prede-
fined) channel 1, for comparison to a frequency transducer. The
displayed frequency actually represents the instantaneous value,
which is updated with each measurement cycle. See Section 3.5.4
for a description of frequency measurements.
“
Vars
” sets the Model 931A to calculate reactive power (vars) based
on voltage, current, and phase measurements from the predefined
inputs. The results are compared to a reactive power transducer.
For three-phase configurations, the display shows the total reactive
power. See Section 3.6.2 for a description of reactive power.
“
Power Factor
” sets the Model 931A to calculate power factor
based on voltage and current from the predefined inputs.
The
results are compared to a power factor transducer.
For three-
phase configurations, the display shows average power factor. See
Section 3.6.3 for a description of power factor measurements.
3.8.1.3
Input Range
Select Input Range from the Transducer Configuration menu and press
the ENTER key to view the available input ranges.
The displayed
67
Содержание 931A
Страница 6: ...vi ...
Страница 12: ...xii ...
Страница 14: ...xiv ...
Страница 16: ...xvi ...
Страница 52: ...SOURCE LOAD B A C N Figure 3 12 3 Phase 4 Wire 3 Element Connections 36 ...
Страница 90: ...Iout I1 V1 V2 V3 I2 I3 Figure 3 17 3 Phase 4 Wire 3 Element Transducer Test 74 ...
Страница 114: ...98 ...
Страница 120: ...104 ...
Страница 142: ...126 ...