
PQ Profiles
The Model 928A can store up to 5 distinct PQ profiles
that may be configured using Mlink software and up-
loaded into the 928A. Profiles are listed in the Model
928A as OFF, USER, PROF-1, . . . , PROF-5.
USER Profile
One profile, called USER, is available only from the
928A keypad. When you select USER, you can set up
one point limit directly in the 928A. Records stored
from USER profile are only available on the 928A itself
and cannot be downloaded.
Profiles - OFF
Select OFF when not using PQ Triggering. Otherwise,
PQ triggering could fill up the available memory. See
Selecting PQ Profiles on following pages.
Working with PQ Profiles and Records
Internal flash memory will store all PQ event records
until flash memory is full, overwritten or erased. View
event records directly from flash on the 928A by press-
ing
PQ
. Changing the PQ profile will not disturb
records already stored in flash memory.
NOTE:
Make sure to download event records us-
ing Mlink software prior to deleting from flash in the
928A.
Selecting PQ Profiles
Except for one PQ profile named USER, all PQ Pro-
files are configured by using Mlink software. Configure
the profile named USER only from the 928A keyboard.
50
Содержание 928A
Страница 1: ...MODEL 928A USER S MANUAL Arbiter Systems Inc Paso Robles CA 93446 U S A ...
Страница 6: ...vi ...
Страница 12: ...xii ...
Страница 14: ...xiv ...
Страница 23: ...Figure 2 Bail Assembly attached to lower holes Figure 3 Bail Assembly attached to upper holes 9 ...
Страница 57: ...Channel B Combined Caution For current probe use see CT Probe Use on page 4 43 ...
Страница 112: ...CT Cable Connector Figure 16 CT Cable Connector side view Figure 17 CT Connector End View 98 ...
Страница 114: ...100 ...
Страница 115: ...CE Mark Certification ...