Arada BK605 Скачать руководство пользователя страница 8

 

Cassette Stove Installation Guide — BK605 Rev 04 

 

 

Masonry Chimney: Built with clay or concrete 

liners, or a chimney block system meeting 

Building Regulations. These types of chimneys 

should be installed in accordance with the 

Building Regulations and BS EN 15287-2:2008 

 

Factory Made Insulated Chimney: Complying 

with BS 4543:Part 2 (often called Class 1 

prefabricated metal chimney). These types of 

chimneys should be installed in accordance with 

Building Regulations and BS EN 15287-2:2008. 

Due to the gradual introduction of European Chimney 

Standards chimneys will be specified according to 

their performance designation as defined in BS EN 

1443 that covers the General Requirements for 

chimneys. The minimum performance designation 

required for use with solid fuel burning stoves is T450 

N2 S D3. 

The flue and chimney installation must be carefully 

checked by a competent person before fitting the 

stove to ensure it is suitable and will work safely. 

If the chimney is old (i.e.: built of brick or stone 

without a liner) or being opened up for reuse 

additional checks and smoke testing as described in 

Appendix E of the Approved Document J 2010 Edition 

should also be carried out to ensure the flue and 

chimney are in good operating condition. 

Check the existing flue is in good condition with 

suitable access for collection and removal of debris. 

It is also important that suitable flue pipe 

(recommended at least 600mm in length) complying  

with the Building Regulations is used to connect the 

stove to the flue in the chimney. Suitable access 

should be provided into the flue for regular inspection 

and sweeping of the flue ways. The installer should 

comply with Building Regulations requirements in 

respect of providing a Notice Plate giving details on 

the chimney, flue lining, hearth and fireplace 

installation. 

Chimneys should be as straight as possible.  

Horizontal runs should be avoided except where the 

rear outlet of the appliance is used, in which case the 

horizontal section should not exceed 150mm in 

length. If necessary a combination of 45° and 90° 

bends can be used as long as the sum of their angles is 

not greater than 180°  in total. i.e. four 45° bends, or 

two 45° and a 90° bend. 

If the stove appears to be working hard but produces 

very little output to the room, it is likely that excess 

draw is present in the flue and that heat is being 

sucked out of the appliance via the chimney.   

To remedy this problem, we recommend fitting of a 

draught stabiliser in preference to a flue damper, in 

the interest of safety and efficiency, together with 

insulating around the exterior of the appliance, this 

will ensure heat loss into the fabric of the building is 

kept to a minimum. 

 

 

FLUES AND CHIMNEYS 

Содержание BK605

Страница 1: ...Cassette stove installation guide BK605 EN 13229 2001 A2 2004 Rev 04 Issue Date 14 11 2018...

Страница 2: ...ed in this manual please contact the Arada retailer in your area or call our technical support department on 44 0 1297 632052 Arada has a policy of continuous product development and therefore we rese...

Страница 3: ...Combustion 6 7 FLUES AND CHIMNEYS 7 8 INSTALLING THE STOVE Removing the door 9 Removing the throat plate and liners 9 Assembling the grate bars 9 Fitting the spigot outlet to the stove 9 Connecting th...

Страница 4: ...en as overriding statutory requirements Arada Ltd will not be responsible for any consequential or incidental loss or injury however caused Health and Safety Before any installation work is undertaken...

Страница 5: ...pliance and 150mm either side of the edge of the appliance In most buildings with solid concrete or stone floors the requirement will be met by the floor itself but mark the hearth to ensure floor cov...

Страница 6: ...positioning of any air vent must be so that it cannot be liable to blockage or obstruction Ideally it should also be positioned where it is unlikely to cause a cold draught It should not be positione...

Страница 7: ...ases are kept warm and that the flue size suits the stove The termination of the outlet at the top of the flue also needs to comply with Building Regulations The minimum effective height of the flue m...

Страница 8: ...k the existing flue is in good condition with suitable access for collection and removal of debris It is also important that suitable flue pipe recommended at least 600mm in length complying with the...

Страница 9: ...e throat plate first to help remove it from its position and to allow it to fit through the opening of the stove Once the throat plate has been removed you can also remove the rear liner s To replace...

Страница 10: ...s and the decorative fire surround and hearth This should be achieved using fire cement Any void surrounding an inset stove when installed should be filled with fire cement vermiculite or similar in t...

Страница 11: ...nce with a lint free cloth or shoe brush to prevent any stains becoming burnt on Check the flue draught which should read 10 20 pa or 0 1 to 0 2 mbar Consult a suitably qualified person who will have...

Страница 12: ...12 Cassette Stove Installation Guide BK605 Rev 04 NOTES Arada Ltd The Fireworks Weycroft Avenue Axminster Devon EX13 5HU United Kingdom Tel 44 0 1297 632050 www aradastoves com...

Отзывы: