Aquasant Messtechnik AG
27
5.3.6
Menu access for parametrisation
All parameters can be adjusted, even after commissioning, in the menu. Double-pressing
the buttons opens the menu structure screen. The following table shows the default values
on initialisation.
Access the menu by pressing the "Test" and "Enter" buttons
&
1 Language
2 OC settings
3 Maintenance
Menu selection 2nd level
Only shows as much text as can be displayed, selection is indented, selection is
scrolling.
Deutsch
English
1 Language selection
deutsch/français/italiano/español/english
If there is no input after 1 min, the display switches to sensor scan
Delay time
on-delay
off-delay
Select delay
If the delay is active, the yellow LED flashes slowly
Delay time:
00.5 s
2-liner with full text
Select delay
Setting range: 0/0.5/1-60 seconds (loop with increments in 1s steps)
Inactive
Year 1
Year 2
Not used in this FW 1.0 version
2. Maintenance service according
Selection: Inactive | 1 year | 2 years | 3 years |reset
Additional setting for DIL switch no. 3
Alarm reactivation
03 week
3. Auto-reset time after acknowledgement of the horn (OUT3 relay) and fault messages
on the display and fault signalling relay.
Setting range: 0-10 weeks
In SIL applications for the higher safety standard, sensor monitoring is even more closely
monitored. The measurement limits for a bad sensor are triggered earlier. Certain
parameters are also disabled, such as sensor function and automatic fault alarm reset.
SIL mode:
inactive
active
7. SIL conformity
Relay 1 function and monitoring
Parameter reset?
no
yes
8. Initialisation with standard operating parameters
Restore the default factory parameters. Language English, and restart the device.
From the menu back to operating mode:
Press the "Reset" button <2 seconds