28
10.4
Communication types
10.4.1
Digital outputs
The digital output has multiple functions, these and their characteristics are described hereafter.
In order to set the parameters, the device must be unlocked with the user code.
Function: Pulse output
for summing (totalizing) the flow volume, compensated volume, mass or Co
2
.
ON
OFF
ms
t
Period
Pulse width
Pulse width (t):
The pulse width limit can be set
between 2…500
ms
(example: 20 ms).
The actual pulse width is dynamically adjusted based on the
current flow, but at least the set value.
The duty cycle is min. 50 %. The off cycle can be bigger
Signal behavior:
The signal is defined as: t = ON and (Period
–
t) = OFF:
Parameters that can be set:
Pulse width (t): 2 - 500 ms
Pulse value (UPP): 0.001 - 1000 units per pulse
Factory setting:
Output1: Pulse value
ltr/p
0.01
Pulse width
ms
20