Minimum and Maximum Operating Voltage
The chiller must operate within specified voltages.
NOTICE
Failure to heed the following may result in damage to equipment.
l
Operating equipment under higher or lower voltage conditions may result in damage to your compressor, motors or
other electrical components. This damage will not be covered by product warranty.
1. Measure site voltage. The site voltage
MUST
be measured under “FULL LOAD” conditions. Activate all
equipment using the same electrical panel as the chiller.
2. If measured site voltage is outside listed ranges, immediately deactivate equipment until site conditions have been
corrected. If unsure of chiller equipment rating, please
see "Identifying Model Specifications" on page 25.
Equipment Rating
Minimum
Site Voltage
Maximum
Site Voltage
A Voltage
(208 to 230 Volts)
Single Phase 60 hertz
200 Volts
253 Volts
B Voltage
(208 to 230 Volts)
Three Phase 60 hertz
200 Volts
253 Volts
D Voltage
(380 to 420 Volts)
Three Phase 50 hertz
361 Volts
441 Volts
G Voltage
(460 Volts)
Three Phase 60 hertz
437 Volts
483 Volts
H Voltage
(200 to 240 Volts)
Single Phase 50 hertz
180 Volts
264 Volts