Page - 31
Configuring Gas Backup
There are two different ways the gas backup heater can be configured.
l
24-hour mode
- commonly used for commercial applications
n
The circulation pump operates continuously.
n
The gas heater will activate if the water temperature falls two degrees below the set temperature. When the set
temperature is reached, the gas heater will be deactivated.
n
The Heat Pump will continue to maintain the set temperature.
l
Scheduled mode
- commonly used for residential applications
n
The circulation pump operates on the circulation pumps regular on-off schedule.
n
The gas heater will activate as needed to ensure that the desired temperature will be reached within the
circulation pumps schedule. The gas heater will deactivate when the water is warm enough to allow the heat
pump to finish within schedule. The heat pump will then continue to heat the water till the set temperature is
reached.
Configure for 24-Hour Mode
Enter "Installer Menus", then proceed
1
-
Ins
ta
lla
tion
Содержание GBB
Страница 2: ......
Страница 25: ...Page 21 Configure Call Flex Enter Installer Menus then proceed 1 Installation...
Страница 29: ...Page 25 1 Installation...
Страница 32: ...Page 28 1 Installation...
Страница 36: ...Page 32 1 Installation...
Страница 37: ...Page 33 Configure for Scheduled Mode Enter Installer Menus then proceed 1 Installation...
Страница 41: ...Page 37 1 Installation...
Страница 43: ...Page 39 1 Installation...
Страница 46: ...Page 42 1 Installation...
Страница 50: ...Page 46 1 Installation...
Страница 53: ...Page 49 1 Installation...
Страница 55: ...Page 51 1 Installation...
Страница 74: ...Page 70 l Follow all National Electric Codes NEC and or State and Local guidelines 3 Appendix...
Страница 75: ...Page 71 3 8 Schematics Some schematics have been provided in the appendix of this manual 3 Appendix...
Страница 77: ......
Страница 78: ......