SPA MODE – HEATING 

 
When operating in spa mode display will show SPA – HEAT on the top line and the actual spa water 
temperature on the second line. 

EXAMPLE:

 

                                                               SPA – 104º 

 

 

To operate in SPA mode user will press the POOL/SPA button (center hand button) once. 
After pressing the POOL/Spa button, the display will show “SPA TEMPERATURE” on the 
top line and the current temperature set point on the bottom line for 5 seconds. Adjust the set 
point by pressing either UP or DOWN until the new set point is reached for spa heating. 

 

The display will revert back to “SPA – HEAT” and the current spa temperature after 5 
seconds of inactivity and the new set point will be stored. 

 

When the spa water temperature falls 1º F below the set point, the control will energize spa 
heating mode (compressor) after the time delay has expired. 

 

During heating once the water temperature reaches the set point, the compressor turns off. 

 
 
 

CHEMICAL USE 

 
 
Water quality must be checked regularly and maintained within recommended limits at all times.  
Failure to maintain the proper water quality will greatly reduce the life of your heater. 
 
 

 Never add chemicals directly into skimmer. 

 Automatic chlorinators must be piped downstream from the heater.  A check valve must be installed 

   between the chlorinator and heater to prevent raw chlorine from draining back into the heater.  A chemical 
   trap may be piped at least six (6) inches above the chlorinator.  See piping diagram B. 
 
 
 

Always maintain the following water quality requirements: 

 
 
 

                     

PH LEVEL  7.4 to 7.8 

       CHLORINE CONCENTRATION  1 to 5 PPM 

TOTAL ALKYALINITY  100 to 200 PPM 
 CALCIUM HARDNESS  100 to 300 PPM

 

 
 
 
 

Содержание Vintage Classic Series

Страница 1: ...R FLOW CONNECTIONS 2 3 ELECTRICAL CONNECTIONS 4 MODES OF OPERATION 5 WIRING DIAGRAMS 6 ELECTRONIC CONTROL PANEL 7 8 CHEMICAL USE 9 START UP 10 11 MAINTENANCE 12 TROUBLESHOOTING CHECKLIST 12 13 CALLING...

Страница 2: ...ion consider the following Heater must be located outdoors Minimum of 24 of clearance on access service side of heater Minimum of 18 of clearance on all three air intake sides of heater Minimum of 48...

Страница 3: ...owed run the filter pump and check the entire system for water leaks Make sure filter is clean and there are no obstructions in the filtering system Proper water flow is essential to the performance o...

Страница 4: ...the bottom of the electrical enclosure using a weather tight fitting A knockout is provided to accept the weather tight fitting Mounting conduit directly to the electrical enclosure will ensure a moi...

Страница 5: ...1 USE COPPER CONDUCTORS ONLY 2 CONNECT FIELD WIRING IN GROUNDED WEATHER TIGHT CONDUIT PER RATING PLATE 3 CONNECT BOND WIRE TO POOL STEEL USING 8 SOLID COPPER WIRE OR LARGER 4 ALL WIRING MUST CONFORM...

Страница 6: ...ed the heater will operate in pool mode The default setting is DISABLED REMOTE THERMOSTAT With this setting you may enable or disable the remote capability In the POOL MODE you will have the capabilit...

Страница 7: ...ge is 10 degrees F or 5 degrees Celsius Default setting is 0 EVAPORATOR SENSOR CALIBRATION With this setting you can calibrate the evaporator temperature reading The calibration range is 10 degrees Fa...

Страница 8: ...stem and to avoid short cycling the compressor During heating once the water temperature reaches the set point compressor is turned off POOL MODE COOLING When operating in pool cool mode the display w...

Страница 9: ...ow the set point the control will energize spa heating mode compressor after the time delay has expired During heating once the water temperature reaches the set point the compressor turns off CHEMICA...

Страница 10: ...al water temperature and the 5 minute time delay is satisfied the compressor will start NOTE Each time the compressor turns off it is protected by a 5 minute anti cycling delay INITIAL HEATING Initial...

Страница 11: ...n Analyzers The heater is equipped with internal devices to monitor and protect the integrity of the unit Should an abnormal condition occur these devices will interrupt the operation of the unit and...

Страница 12: ...f the finish Winterizing When the heater is exposed to freezing temperatures it is essential that all water within the unit be properly drained When water freezes it expands damaging piping Turn therm...

Страница 13: ...r is dirty or clogged Shortage of water to pump air leak Undersized pump Valves not in correct position Filter in backwash mode Water pressure switch needs adjustment or is defective HIGH REFRIGERANT...

Страница 14: ...IES LLC A factory representative will assist you or your serviceman over the phone SERVICE PERFORMED WITHIN THE WARRANTY PERIOD MUST BE APPROVED BY AQUA COMFORT TECHNOLOGIES LLC PRIOR TO SERVICE BEING...

Отзывы: