SYSTEM SPECIFICATIONS 48 AND 51 

NXT SERIES

Generic Meter Guidelines

Open collector output

Pulse rate generated must not exceed 100 pulses per

second (100 Hz), or 6,000 pulses per minute

Support for meter outputs in the range of 1-255 gallons

(25.5 m

3

) for every 1-255 pulses 

Example: 35 gallons/100 pulses  

(=3.5 gallons/10 pulses, = 0.35 gallons/1 pulse)

Meter must operate at 5 VDC

Electrical Rating

115 VAC ±20% input, 24 VAC output w/50 VA (maintain

input voltage in this range)

230 VAC ±20% input, 24 VAC output w/50 VA (maintain

input voltage in this range)

Max Rated Power 15W

Humidity

95% RH, non-condensing

Temperature

• Maximum control fluid temperature 140°F (60°C)

Operate where ambient temperatures are above 32°F

and below 110°F

Pressure

• Maximum control fluid pressure 125 psi (8.5 bar)
• Control fluid can be either water or air and must be equal

to or greater than system pressure.

NXT STAGER DIMENSIONS

(6X) 1/8" NPT PORT 60  APART

48ES STAGER

51ES STAGER

(8X) 1/8" NPT - 45  APART

ø 

0.733 [18.62 mm]

4 places

ø 

0.88 

[22.4 mm]

11.13 [282.7]

10.50 [266.6]

5.25 [133.4]

1.41 [35.8]

2.45 [62.2]

2.06 [52.3]

2.75 [69.9] 2.75 [69.9]

4.00 [101.6]

2.00 [50.8]

2.72 [69]

3.50 [88.9]

6.42 [163.1]

1.25 [31.7]

6.00 [152.4]

(4X) R.16 [4]

(4X) .19 [4.8]

.32 [8.1]

11.13 [282.7]

1.75 [44.4]

Optional 

Solenoid

8.91 [226.3]

1/8" NPT Drain

1/8" NPT Filtered Inlet

1/8" NPT Drain

1/8" NPT Filtered Inlet

1/8" NPT Drain

ø 

0.733 [18.62 mm]

4 places

ø 

0.88 

[22.4 mm]

*

*

*

*

Figure 1 

*

NOTE: Drill as required. These holes

 will only be drilled at factory if 

 required.

 NXT Stager Controller     AU11

Содержание NX48

Страница 1: ...guide for service of the controller only System installation requires information from a number of suppliers not known at the time of control manufacture This product should be installed by a plumbin...

Страница 2: ...ure 140 F 60 C Operate where ambient temperatures are above 32 F and below 110 F Pressure Maximum control fluid pressure 125 psi 8 5 bar Control fluid can be either water or air and must be equal to o...

Страница 3: ...s flow meter sensor input Regeneration of a unit will begin after the other control has left Standby and returned to Service When the Regeneration cycle is complete the regenerated unit will enter Sta...

Страница 4: ...Three Meters 1 2 3 4 5 The third tank returns to Standby as demand decreases past the second trip point Standby Flow Split Between Two Meters 1 2 3 4 6 Tanks return to Standby due to decreased total...

Страница 5: ...n Service LCK Lock Lock will be displayed when contact closure is applied across the interlock terminals on the circuit board See the Network Communication Cables Connections section of this manual LE...

Страница 6: ...mer is fully inoperative and any calls for regeneration are delayed The timer upon power re application resumes normal operation from the point that it was interrupted NOTE A flashing Time of Day disp...

Страница 7: ...ress 2 Second Control Valve Default Valve Address 3 Third Control Valve Valve Address 4 Fourth Control Valve SYSTEM TYPE 4 SINGLE UNIT Options System 4 single unit System 5 2 4 units Parallel Interloc...

Страница 8: ...Hours Minutes Seconds CYCLE 4 OFF Example Off Default 48 00 Stager CYCLE 4 00 12 00 Example Refill 00 12 00 Default 51 09 Stager Hours Minutes Seconds CYCLE 5 OFF Example 2 to 998 gpm 1 to 3997 Lpm 3...

Страница 9: ...s resumed 3 Push and release the D button at anytime during diagnostic mode and the timer will exit the mode 4 Depending on the current controller programming certain displays may not be able to be vi...

Страница 10: ...Start c c c c c c c c c c c c c c c c c c c c c Aux Relay Output End c c c c c c c c c c c c c c c c c c c c c Chemical Pump x x x x x x u u x x x x x x x x CPO Aux Relay Volume c c c c c c c c c c c...

Страница 11: ...ould be left open or discharged to unrestricted or open drain DO NOT plug or restrict drain port 3 Connect the 1 8 NPT control ports to appropriate valves Refer to tubing schematic provided in the Plu...

Страница 12: ...Note C Program Cycle 2 time to 00 00 00 for filter operation 4 POSITION FILTER Drain Line Flow Control not shown Note B Inverted Stager types will have these ports pressurized Inverted Stager to be us...

Страница 13: ...DRAIN 2B UNIT B 4B 6B 1B 3B RAW WATER To Additional Tanks As Required SERVICE NOTE All valves normally open pressure to close NOTE Valve 2 for each tank is controlled by solenoid for system 7 9 14 NOT...

Страница 14: ...installed at the factory is a universal type It is plumbed in an energize to close configuration when service outlet valve is normally open When a tank enters Regeneration or Standby the solenoid is...

Страница 15: ...1 ES NEMA4 Solenoid 61784 Kit 48 51 ES 3214 NXT CKT Board Keypad 61764 Cable Assy Communication CAT 5 5 Meters Long 1075499 Switch Micro 40941 Wire Harness Upper Drive 1075502 Wire Harness 2nd Aux Swi...

Страница 16: ...WIRING DIAGRAM 48 51 NXT STAGER CONTROLLER NXT Stager Controller AU11...

Страница 17: ...No power to Control 3 Power Control 3 Communication Cable to Valve Address 3 bad or missing Connect or replace Communication Cable Detected Error No Message 4 No power to Control 4 Power Control 4 Com...

Страница 18: ...AQ Matic or its affiliates All other registered and unregistered trademarks and logos are the property of their respective owners Because we are continuously improving our products and services AQ Ma...

Отзывы: