5
Programming
General
Using the controls in programming mode:
Icon
Description
Designation
Function in programming mode
Horn
acknowledgement
HQ
Navigation up
Alarm acknowledge
LQ
Switch
Lamp test
LT
Navigation down
The programming mode is started as follows:
Power up the unit and push the HQ and LT keys at the same time within 10
seconds. If no other keys are pressed within 5 seconds, LSE-D16 will switch
back to operating mode. If additional keys are pressed, the programming mode
remains active for 30 seconds. If no other key is pressed for 30 seconds, LSE-
D16 will return to operating mode and will take over the programming. The
programming mode can be ended by pushing the HQ and LT keys. The
settings are saved. While the programming mode is active, the power LED
blinks green.
Programming levels
LSE-D16 Operation-/Fault indicator has 6 programming levels:
1. Inputs group 1 (red): Normally open / closed switchover
2. Inputs group 1 (green): Normally open / closed switchover
3. Virtual DIP switch: time delays and system settings
4. Activation LT-Output as Common Output Priority 2
5. RGB-Colour setting inputs group 1
6. RGB-Colour setting inputs group 2
Levels 4 to 6 are deactivated in the factory settings.
They can be activated in level 3 with the virtual DIP switch 16.