SySAlM
Air filter alarm status
Humidifier alarm status
Dehumidifier alarm status
HVAC system alarm status
COS: C14
Permissions: Read/Write
Query
Command
Syntax:
SN[#] [alarm]ALM?<CR>
Description: Requests the
[alarm]
alarm status .
Assignment
Command
Syntax:
SN[#] [alarm]ALM=[value]<CR>
Description: Sets the
[alarm]
alarm status to
[value]
.
Examples:
SN1 WPALM=ON<CR>
SN1 DEHALM=OFF<CR>
Response or
COS Message
Syntax:
SN[#] [alarm]ALM=[value]<CR>
Example:
SN1 FLTALM=OFF<CR>
Node address 1 responds with an air filter alarm status of OFF .
Parameters
Range
alarm:
alarm command code
[FLT, WP, DEH, SYS]
value:
alarm status
[OFF, ON]
OFF:
the [alarm] alarm is not active
ON:
the [alarm] alarm is active
The alarm statuses can be cleared through the Setup Screens and Menu Screens . When an assignment command is received with the value
parameter set to OFF and the specified alarm is active, the respective alarm is cleared and reset if the alarm period is not set to OFF . When
an assignment command is received with the value parameter set to ON and the specified alarm is not active and the specified alarm period
is set to OFF, the respective alarm is activated and displayed on the screen . If the alarm status is changed at the node, a C14 COS unsolicited
message is issued (if C14 is ON) .
HUMTyP
Humidifier type
COS: N/A
Permissions: Read/Write
Query
Command
Syntax:
SN[#] HUMTYP?<CR>
Description: Requests the humidifier type setting .
Assignment
Command
Syntax:
SN[#] HUMTYP=[value]<CR>
Description: Sets the humidifier type setting to
[value]
.
Example:
SN1 HUMTYP=0<CR>
Response
Syntax:
SN[#] HUMTYP=[value]<CR>
Example:
SN1 HUMTYP=0<CR>
Node address 1 responds with a humidifier type setting of flow-through .
Parameters
Range
value:
humidifier type setting code
[0 – 1]
0:
flow-through type
1:
drain-less type
26