- 17 -
2. Run a 2-wire cable from the sensor to the thermostat.
3. Take a resistance measurement before connecting to the
ODT and CIR GND terminals to verify the sensor is
properly installed. Measure the wires at the thermostat to
account for wire splices.
• Use an ohmmeter to measure the resistance (k
Ω
) of
the sensor. The resistance reading will depend on the
outdoor temperature (see table).
4. Wire the sensor to the thermostat (see
Figure 7
).
• Strip 1/4" of insulation from the two sensor wires.
• Connect the sensor wires to the ODT and CIR GND
terminals of the thermostat. The wiring is not polarity
sensitive, so either wire can be connected to either
thermostat terminal.
CAUTION
Do not run the wire along side line
voltage (120 VAC) or higher lines as this can cause
erratic readings.
OUTDOOR TEMPERATURE (°F)
RESISTANCE (k
Ω
)
-30
230.6
-20
163.8
-10
117.6
0
85.4
10
62.6
20
46.3
30
34.6
40
26.1
50
19.9
60
15.3
70
11.9
80
9.4
90
7.4
100
5.9
Содержание 8570
Страница 13: ... 9 Diagram 1 Single Stage Furnace and AC ...
Страница 14: ... 10 Diagram 2 Two Stage Furnace and AC ...
Страница 15: ... 11 Diagram 3 Two Stage Roof Top Unit ...
Страница 16: ... 12 Diagram 4 Boiler with AC ...
Страница 17: ... 13 Diagram 5 Radiant Floor 1st Stage Heat with Furnace 2nd Stage Heat and AC ...
Страница 18: ... 14 Diagram 6 Single Stage Heat Pump ...
Страница 19: ... 15 Diagram 7 Two Stage Heat Pump ...
Страница 22: ...CIR GND IDS ODT ZA ZB C Figure 7 18 ...
Страница 26: ... 22 CIR GND IDS ODT ZA ZB C Figure 9 ...
Страница 40: ...DP 10006198 01 05 B2203358B Printed in U S A P O BOX 1467 MADISON WI 53701 1467 ...