background image

INSTALLATION INSTRUCTIONS

LOCATION
To ensure proper operation, the thermostat should be
mounted on an inside wall in a frequently occupied
area of the building. In addition, its position must be
at least 18" (46cm) from any outside wall, and approx-
imately 5' (1.5m) above the floor in a location with
freely circulating air of an average temperature.
BE SURE TO AVOID THE FOLLOWING LOCATIONS:
- behind doors or in corners where freely circulating

air is unavailable

- where direct sunlight or radiant heat from appli-

ances might affect control operation

- on an outside wall
- adjacent to, or in line with, conditioned air dis-

charge grilles, stairwells, or outside doors

- where its operation may be affected by steam or

water pipes or warm air stacks in an adjacent parti-
tion space, or by an unheated/uncooled area
behind the thermostat

- where its operation will be affected by the supply

air of an adjacent unit

- near sources of electrical interference such as arc-

ing relay contacts

THERMOSTAT INSTALLATION

1. Insert a flat blade screwdriver or coin 1/8" into the

slot located in the bottom center of the thermostat
case and twist 1/4 turn. When you feel or hear a click,
grasp the case from the bottom two corners and sep-
arate from the subbase as shown in the diagram at
the right. Some models require more force than oth-
ers when separating due to the number of terminals
on the subbase.

2. Swing the thermostat out from the bottom.

3. Lift the thermostat up and off the subbase.

4. Place the rectangular opening in the subbase over the

equipment control wires protruding from the wall and,
using the subbase as a template, mark the location of
the two mounting holes (exact vertical mounting is
necessary only for appearance).

5. Use the supplied anchors and screws for mounting on

drywall or plaster; drill two 3/16" (5mm) diameter
holes at the marked locations; use a hammer to tap
the nylon anchors in flush to the wall surface and fas-
ten  subbase using the supplied screws. (Do not over-
tighten!)

6. Connect the wires from your system to the thermo-

stat terminals as shown in the wiring diagrams.
Carefully dress the wires so that any excess is
pushed back into the wall cavity or junction box.
Ensure that the wires are flush to the plastic subbase.
The access hole should be sealed or stuffed to pre-
vent drafts from affecting the thermostat.

REPLACING THE THERMOSTAT

ON THE SUBBASE

1. Position the thermostat on the hinged tabs located at

the top of the subbase.

2. Gently swing the thermostat down and press on the

bottom center edge until it snaps in place.

SPECIFICATIONS

Rated Voltage

20-30 VAC, 24 nominal

Rated

0.08 Amps to 1.5 Amps continuous

Current

per output with surges to 4 Amps Max.

Control

Heating: 38° to 88°F in 1° Steps

Range

5° to 30°C in 1° Steps

Thermostat
Measurement

28° to 124°F or 0° to 48°C

Range

Control

±.5° C at 20°C

Accuracy

±1°F at 68°F

NOTE: This thermostat contains electronic circuitry
replacing the conventional mechanical anticipator.

RH

W

Line
Voltage

24 VAC

Transformer

8531

W1

OUTPUT TERMINAL FUNCTIONS

RH . . . . . . .24 VAC supply from heating

equipment

W  . . . . . . .Heat energized with a heating call

4 MINUTE 

(MIN ON/OFF)

KEYBOARD UNLOCKED

2 MINUTE 
(MIN ON\OFF)

KEYBOARD LOCKED

OFF     ON

P.O. BOX 1467 • MADISON, WI 53701-1467

CALL 608/257-8801 • FAX 608/257-4357

Products For Better Indoor Air Quality.

Отзывы: