APQ S.A. R-120 HP Скачать руководство пользователя страница 3

CHECK 

Regulator without VIS and without VES 

 

Check that the valve (V1) at the inlet to the regulator (R), the valve (V3) at the outlet to the regulator and the bleed 

valve (V2) are closed. 

 

Slowly open the inlet valve (V1) and use the pressure gauge (M1) to check that the pressure is correct at the inlet to the 

regulator (R). Use the pressure gauge (M2) to check that the pressure increases at the inlet to the regulator (R) until it 
is stabilised to the adjusted pressure in the regulator (R). 

 

Close the inlet valve again (V1) 

 

Use the inlet pressure gauge (M1) to check that there are no leaks at the inlet to the regulator (R) 

 

Use the outlet pressure gauge (M2) to check that there are no leaks at the outlets of the regulator (R) 

 

Regulator without VIS and with VES 

 

Make the adjustments described above 

 

Connect an external source of pressure via the bleed valve (V2) in the tank located along the stretch between the outlet 

to the regulator (R) and the outlet valve (V3). 

 

Slowly increase the pressure until the VES is activated. If it is necessary to vary the firing point of the VES, make the 

appropriate adjustments at the inspection hole (4)   
 

Regulator with VIS at minimum 

 

Make the adjustments described above 

 

Start up the regulator (R), checking that the outlet has the correct regulation pressure. 

 

Close the gas inlet valve (V1) and slowly reduce the pressure to the outlet via the bleed valve (V2) until the minimum 

pressure VIS valve is activated. If it is necessary to vary the firing point of the VIS, make the necessary adjustments at 
the inspection hole (9)   

 
 

Regulator with VIS at maximum 

 

Make the adjustments described above 

 

Connect an external source of pressure via the bleed valve (V2) in the tank located along the stretch between the outlet 

to the regulator (R) and the outlet valve (V3). 

 

Slightly  increase  the  pressure  in  the  tank  until  you  see  that  the  VIS  maximum  pressure  valve  is  activated.  If  it  is 

necessary to vary the firing point of the VIS, make the necessary adjustments at the inspection hole (8).   

 

PROBLEMS, CAUSES AND SOLUTIONS 

The regulator does not close 

 

Dirt in the regulating bar 

o

 

External filter (F1) in poor condition, clean filter and closing bar 

 

Damaged rubber seat disc or orifice 

o

 

Replace regulator 

 

Internal mechanism dirty or worn 

o

 

Replace regulator 

 

The maximum pressure safety valve discharges 

 

The seat disc or orifice it is not watertight 

o

 

Possible dirt in the seat disc 

 

Water hammering at the outlet, due to abrupt closure of electro valves or manual shut-off valves 

o

 

Small tank outlet 

o

 

Reduce this effect by installing a VES valve in the regulator outlet tank. 

 

Where there is no flow, increase the temperature in the outlet stretch due to the sun or nearby sources of heat. 

o

 

Eliminate sources of heat and activate the VES below the maximum VES 

 

The minimum pressure safety valve discharges 

 

The outlet pressure is adjusted below or very close to the minimum safety adjustment level 

o

 

Reduce the taring of the minimum VIS 

 

Excessive flow for the inlet and outlet pressure values available in the regulator. 

o

 

Lower the flow requested. 

o

 

Increase the inlet pressure. 

 

Very high instant consumption 

o

 

Raise the volume of the tank situated at the regulator outlet 

Содержание R-120 HP

Страница 1: ...talling the regulator ensure that The regulator selected see label coincides with the needs of the installation The fluid passes through the body of the regulator in the correct direction as indicated on the arrow on the body of the regulator The tubing has been previously clean and the gas reaches the regulator perfectly clean and dry The regulator must positioned so that there is sufficient room...

Страница 2: ...sh opening the shutoff valve V1 slowly located at the filter inlet F1 Slowly finish opening the shutoff valve V3 located downstream from the regulator Close the bleed valve V2 The time required to press down the button opening the internal bypass will depend on the differential of pressure between the inlet and outlet and the volume of the outlet tank ADJUSTMENTS Regulators are supplied with sprin...

Страница 3: ...he necessary adjustments at the inspection hole 9 Regulator with VIS at maximum Make the adjustments described above Connect an external source of pressure via the bleed valve V2 in the tank located along the stretch between the outlet to the regulator R and the outlet valve V3 Slightly increase the pressure in the tank until you see that the VIS maximum pressure valve is activated If it is necess...

Страница 4: ... 000000 000 a 000 R 120ES ZM3 00 000000 250 to 600 R 120ES ZM3 00 000000 000 to 000 R 120ES ZM3 00 000000 400 to 800 R 120HP ZM3 00 000000 000 to 000 R 120HP ZM3 00 000000 700 to 1800 R 120HP ZM3 00 000000 000 to 000 R 120HP ZM3 00 000000 1600 to 4000 R 120HP ZM3 00 000000 000 to 000 VIS MAXIMUM MINIMUM ADJUSTMENT SPRINGS Wdo maximum Spring code Adjustment field in mbar ZM3 00 000000 000 to 000 ZM...

Отзывы: