Applied Energy Solutions WorkHorse Series 1 Скачать руководство пользователя страница 2

APPLIED ENERGY SOLUTIONS WorkHorse Series 1

INDUSTRIAL BATTERY CHARGER OWNER’S MANUAL

INSTALLATION: READ AND FOLLOW ALL SAFETY INSTRUCTIONS ON THE FOLLOWING PAGE. All AES SERIES 1 chargers are for 
indoor use only. Charging areas must be clean, dry and free from combustible materials, and/or open flames. Charging areas must be 
properly ventilated and smoking should never be allowed in or near the charging area. The temperature of the charging room should be 
between 32

o

 F and 104

o

 F.

CAUTION 

To reduce the risk of fire, use only on circuits provided with branch circuit protection indicated in Table 1 (page 2) in

 

accordance with the NATIONAL ELECTRIC CODE ANSI/NFPA 70.

MOUNTING: SERIES 1 chargers must be mounted on a surface constructed from con-combustible material, such as stone, brick, 

concrete or metal.

INPUT POWER CONNECTION: The INPUT POWER is to be connected via the supplied line cord or to the short 10 AWG “pigtails”

(consult Table 1).

Battery charging products can cause serious injury, death or damage to other equipment and property if the safety rules are not strictly

followed.

SERIES 1 CONTROL FEATURES:
1.

Automatic five-second delayed start upon connection of a properly sized battery.

2.

Battery voltage is continually monitored.

3.

Automatic charge termination 3 hours after the 80% charge point.

4.

80% charge point selectable 2.37 or 2.45 volts per cell.(consult factory representative for 2.45 vpc setting procedure)

5.

On / off Equalize switch provided to extend charge 3 additional hours after normal charge termination.

6.

Backup timer - 12 hours to the 80% point.

7.

Automatic fault shut down: displayed numerically on the 2 digit LED readout:

a.

Fault code 1 

- Low volts per cell - less than 1.7 vpc

b.

Fault code 2 

- High volts per cell - greater than 2.7 or 2.80 vpc (set with 80% point)

c.

Fault code 3 - 

Battery disconnected from charger during charge

d.

Fault code 4 

- Charge time exceeded - backup timer expired

e.

Fault code 5 - 

Low charging current - charging current less than approximately 3 amps

8.

Memory retention during AC power loss.

9.

Refresh cycle (optional) - 30 minutes every 24 hours. (consult factory representative for setting procedure)

10. Delay start (optional) - 1 hour non-resettable (consult factory representative for setting procedure)
11. Automatic LED test - All LED’s flash alternate red / green upon AC power and battery connection.
12.

Fault code 0 - 

Manual stop button - used to end the charging process

13. Displays:

a. 2-digit LED readout - displays charging current and Fault codes.
b. Equalize LED - on solid when unit is set to equalize, flashes when unit is in equalize charge mode.
c. Shutdown LED - on solid when charger has completed a normal charge cycle, flashes when a fault has occurred.

INPUT VOLTAGE CHANGEOVER: If the charger is capable of more than one input voltage consult the attached schematic and 

changeover label inside the charger to reconfigure the charger as required. Be sure to reconfigure both the power transformer taps and 

control transformer voltage switch, and replace the line cord and plug assembly with one rated per the NATIONAL ELECTRIC CODE and

Table 1.

OPERATING PROCEDURE: Verify that the charger is wired for the input AC source available. Connect the charger to AC source. The 

charger’s 2 LED’s will flash several times and a “0” (zero) will scroll across the LED display.

Connect a properly sized (same cell number and amp-hrs size) battery to the charger. The charger LED’s will again flash several

times. If the charger and battery are matched and all are in good working order, the charger will start charging and display the charging 

current on the digital LED display. If the charger and battery are mismatched or either is defective the charger will shutdown and display a

fault code. Consult the charger front panel label for fault codes.

The charger will automatically terminate the charge cycle 3 hours after the 80% point is reached unless the equalize button is 

pressed or a fault condition occurs. After a normal charge completion the charger will return to displaying the sequencing zero. The battery

can now be safely unplugged since all charging has stopped. If the charger was still in charge mode, pressing the STOP button will 

terminate the charging process and allow the battery to be safely unplugged.

Содержание WorkHorse Series 1

Страница 1: ...FERRORESONANT BATTERY CHARGERS Installation and Operating Instructions Applied Energy Solutions LLC One Technology Place Caledonia New York 14423 585 538 4421 www appliedenergysol com The Power of Excellence FM1246 REV G ...

Страница 2: ...C power loss 9 Refresh cycle optional 30 minutes every 24 hours consult factory representative for setting procedure 10 Delay start optional 1 hour non resettable consult factory representative for setting procedure 11 Automatic LED test All LED s flash alternate red green upon AC power and battery connection 12 Fault code 0 Manual stop button used to end the charging process 13 Displays a 2 digit...

Страница 3: ...THEM TO BURST AND CAUSE INJURY TO PERSONS AND DAMAGE TO PROPERTY UTILISER LE CHARGEUR POUR CHARGER UNE BATTERIE AU PLOMB UNIQUEMENT CE CHARGEUR N EST PAS CONCU POUR ALIMENTER UN RESEAU ELECTRIQUE TRES BASSE TENSION NI POUR CHARGER DES PILES SECHES LE FAIT D UTILISER LE CHARGEUR POUR CHARGER DES PILES SECHES POURRAIT ENTRAINER L ECLATEMENT DES PILES ET CAUSER DES BLESSURES OU DES COMMAGES 6 NEVER C...

Страница 4: ...Applied Energy Solutions 1 Technology Place Caledonia NY 14423 ...

Страница 5: ...Applied Energy Solutions 1 Technology Place Caledonia NY 14423 ...

Страница 6: ...NS option the replacement of the defective product APPLIED ENERGY SOLUTIONS and its authorized agents shall not be liable for direct or indirect damages in excess of such repair or replacement In no event shall the purchaser be entitled to recover for contingent expenses from but not limited to telephone calls telegrams travel expenses lodging duties and taxes labor rental or replacement equipment...

Отзывы: