7.Abnormal heating protection function description:

   
    
         

      

Schematic diagram of the working principle of “abnormal heating protection function” 

           (set A=OFF/t=20 minutes):

Continue heating for 20 minutes

.

 

POWER ON

.

PV

SV

Program records
 the current temperature

 value (P1=20.5°C)

.

PV

SV

Program records the
 current temperature 

value (P2=30.0°C)

.

note:
In the timing process, if the heating reaches the set value (stop heating), 
the timing will be cleared; if the heating range is 

3°C, no alarm will be generated.

≥ 

    

When the timing is over and the temperature rise is less than 3°C (P2-P1 < 3°C), 

  the program considers this heating to be an "abnormal heating" behavior.

Cyclic heating

8.Some examples of functional applications of the 
meter include:

   
    
         

11.Instrument alarm or fault display code meaning:

"

Abnormal warming protection function" is mainly to solve the customer's response to the turtle 

box in the constant temperature process temperature probe exposed to the water due to other 
factors or in the water change, maintenance process temperature probe forget to put into the 
water, the risk of development and protection of the development of protection Sex program 
features. It is mainly determined by comparing the measured temperature value and the 
continuous warming time at different periods of the heating process. When the instrument 
considers this abnormal heating, the output of the relay is first turned off and the instrument 
immediately stops heating. At the same time, the PV window displays the fault code “EP” and 
continues beeping. Remind users of abnormal heating. Users should promptly investigate the 
cause of the failure. After unplugging the power plug of the meter and plugging it in again, the 
meter may be released from the locked state and the normal heating control may be resumed.

1. When the temperature probe is not placed in the water or the probe 
accidentally leaves the water:

2. when the heater is not heated when the alarm:

3, water shortage anti-dry protection:

      When the meter starts to warm, the program records the current temperature 
measurement and the timer program starts timing. Since the temperature probe 
is not in the water, the measuring temperature of the meter will hardly change or 
decrease.When the time reaches the preset t time, the temperature difference 
between the measured temperature and the starting temperature is 

3°C. 

When it is reached,it is a normal warming state. If it does not reach this condition, 
it is regarded as an abnormal warming behavior. Then, the program will stop 
heating information, lock the fault, and beep at the same time. The user is 
reminded that the temperature probe is out of the water and there is a danger of 
heating.

  When the instrument is operating in a constant temperature process, if a 
problem occurs in the heater and the heating cannot be normally performed, the 
timing program starts timing after the program performs a warming action. 
Because the heater malfunctions, the measured temperature of the instrument 
will hardly change or decrease. When the time reaches the preset T time, the 
difference between the temperature measured at this time and the temperature 
value at the beginning of warming is 

3°C. When it is reached, it is a normal 

warming state. If it does not reach this condition, it is regarded as an abnormal 
warming behavior. Then, the program will stop heating information, lock the fault, 
and beep at the same time. Remind users of 
problems with the heating system.

       Enabling this feature requires a "water level switch" to be implemented. 
When the water level in the water tank falls to the trigger point of the “water level 
switch” or the water in the tank is lost due to unknown reasons, the meter 
program will turn off the heating output. The PV digital pipe on the upper window 
displays the fault code “ES” and the “water level” indicator point. Light and beep 
alert. Remind the user of abnormal water levels in the tank.

≥ 

≥ 

9.Instrument wiring diagram description:

   
    
         

TYPE:CL-809A 
TEMP:-20 120

POWER:220VAC 50HZ

/

Over temperature
 sensor

50K  NTC

220VAC

note:
Socket output maximum power 800W

Temperature 
sensor

Output socket

Power plug

50K  NTC

220VAC

If the wiring diagram of the instruction manual is not consistent with the wiring
 diagram on the meter housing, the wiring diagram on the housing shall prevail.
 When the power of the external heater is too large, in order to ensure the safety
 and long-term stable operation of the heating system, externally switching 
high-power AC contactors may present potential safety hazards.

10.Water level switch accessories and installation notes:

1. The water level switch (liquid level switch) has a wide variety of shapes 
and can be equipped with water level switches suitable for installation 
according to the requirements of their own site.

2, the water level switch is best installed by a professional electrician, 
when installed, the water level switch should be vertical or horizontal with 
the water surface, can not have a large tilt angle; water level switch 
installation site must have a cofferdam, to touch the water inside the turtle 
and other animals caused by mistake Action; regular cleaning of debris in 
the cofferdam to prevent water level switch can not normally detect the 
water level.

Maximum range

The “LLL”character appears when the 

temperature probe is damaged or has a large 
value, reminding the user to replace the new 
temperature probe.

Ultra minimum range

The “HHH” character appears when the 

temperature probe is damaged or has a large 
value, reminding the user to replace the new 
temperature probe.

Upper limit over 

temperature alarm

Exceeding the upper limit alarm setting will 

result in the “EH” character, the 
simultaneous turning off of the output and a 
beep alarm.

Lower limit over-

temperature alarm

Exceeding the lower limit alarm setting will 

result in an “EL” character and a beep alarm.

Higher deviation over 

temperature alarm

Exceeding the upper deviation alarm setting 

will result in the “Eb “character, the 
simultaneous turning off of the output and 
the buzzing alarm

Lower deviation over 

temperature alarm

Exceeding the lower deviation alarm setting 

value will cause “EA” characters and beep 
alarms at the same time.

Out of range alarm

If the alarm setting value exceeds the range, 

the “EE” character and the buzzer alarm will 
appear.

Abnormal warming 

alarm

When the “abnormal heating” condition is 

reached, the “EP” character will appear and 
the output will be turned off and beep alert

Water level alarm

If the water level is too low or there is a lack 

of water, the “ES” character will appear and 
the output will be turned off and the beep 
alert will be turned off.

12.installation and use precautions Description:

1, in order to prevent high-frequency interference, the probe line can not be 
with the power line or output power line together amount away from the power
 or power line, there is space to separate wiring.

2. The instrument drives high power load (more than 800W), it is best to connect 
the relay or AC toucher. To extend the life of the instrument's internal relays.

3, if you want to extend the probe line due to installation reasons, the longest 
can not exceed 100 meters.

4, in order to ensure the normal use of the instrument, please avoid in a 
corrosive, flammable, explosive, damp used in harsh environments.

5. After the instrument software/hardware function is upgraded, please refer
 to the latest version specification. .

6, Factory equipped with accessories: integrated temperature controller,
 a manual. Instrument use such as abnormal, please first check the 
instructions or call the factory after-sales technical support phone for 
technical support 0086-15107613940/E-MAIL: [email protected]

Small float

level switch

Отзывы: