Output socket

220V power plug

CL-809A Farming (turtle, fish, snake) intelligent temperature control thermostat

First of all, thank you for using this company's quality products,

 Please read this manual carefully before use, so that you can fully understand and correctly use the instrument (software version V2.0)

1.Shape and panel description:

   
    
         

     Appearance size: 137mm (high) * 75mm (width) * 40mm (thickness)

2.Features:

   
    
         

3.Technical Parameters:

   
    
         

5.Instrument function description

OUT output light

OUT

OUT

CL 809A

-

6.Parameter setting flow chart:

Correct wiring

Power on

 

normal 

  display

 

Alarm 

value

 

Click "    " or "     " button

 

control

 method

 

 

control

Return 

difference

 

Sensor 

correction

 

Alarm 

method

 

Lowest 

range

 

Highest 

range

Press the "       " and "      " 
keys simultaneously for 
about 10 seconds to 
enter the field parameter
 group or engineering
 parameter group to view
 and set

 
 

Temperature
Setting value

 

Press "       " or

"        " key modification

 

Wait 3 seconds to automatically

 save and exit the setting

 

Parameter

        lock

hold the “     ” key for
 about 2 seconds

 

Auxiliary 

protection

 function

 

Timing time

 

Parameter

        lock

hold the “     ” key for
 about 2 seconds

hold the “     ” key for
 about 2 seconds

hold the “     ” key for
 about 2 seconds

hold the “     ” key for
 about 2 seconds

hold the “     ” key for
 about 2 seconds

hold the “     ” key for
 about 2 seconds

hold the “     ” key for
 about 2 seconds

hold the “     ” key for
 about 2 seconds

hold the “     ” key for
 about 2 seconds

hold the “     ” key for
 about 2 seconds

set LCK 12

 

=

set LCK 112

 

=

1, dual digital display / dual set / dual sensor / dual relay integrated intelligent 
temperature controller, used in aquaculture (turtle, fish, snakes) industry temperature
control. Supporting water level switch can achieve water shortage heating protection.

2. The thermostat uses an integrated digital module LED display, using touch buttons, 
simple operation,

3, heating / cooling function mode free switch, with temperature probeself-diagnosis
there are a variety of alarm mode selection.

4 Plug-type power supply and socket-type output mobile temperaturecontrol system, 
convenient for users to use in different occasions, eliminating complicated wiring, 
easy to use

5, power supply line all use BVR1.5 more than pure copper wire, supporting 
air-conditioning dedicated high-power socket to maintain the long-term safe operation 
of the heating system, product durable and reliable.

1, Working power: 85 ~ 265VAC 50/60HZ.
2, temperature sensor: 50K NTC.
3, temperature display range: -40.0 °C ~ +120 °C, resolution: 0.1 °C (-9.9 ~ 99.9 °C)
4, temperature control range: -20.0 °C ~ +110 °C, resolution: ± 1 °C.
5, working environment: -10 °C ~ +60 °C, relative humidity: 20% ~ 85% 
(no condensation).
6, the main control relay contact capacity: normally open contact 10A 
(recommended load: cooling 0.5 horses, heating 800W)

Symbol

Parameter 

name

Predetermine

d area

Initial 

value

Description

Short press "      " or "         " key to enter the control temperature setting state (LCK=1).

SV

Setting value

CL--CH

30.0

Set the required temperature control target value

(

18 --35 )

Press the "        " and "          " keys at the same time for about 10 seconds to enter the engineering parameter view and set (LCK=12)

LCK

Parameter lock

0-199

1

LCK=0, all parameters cannot be modified
LCK=1, only the SV reference value can be modified.
LCK=12, all parameters can be modified
LCK=112, enter the engineering parameter group to modify

AL

Alarm value

-40~+120

3.0

Set alarm value

Fd

control method

F/D

F

F: heating control, D: cooling control.

bd

Master control 

difference

0.0~10.0

0.5

Set master control relay operation backlash

SC

Sensor 

correction

-

+

10.0~ 10.0

0.0

Set the measurement error due to the sensor

AP

Alarm method

H/L/b/A/E
n

/

b

H: Upper limit alarm, L: Lower limit alarm.
b: Upper deviation alarm, 
A: Lower deviation alarm.
E: Out of range alarm. n: No alarm function.

CL

SV minimum 

setting

-

+

40~ 120

18

Limit the minimum set temperature of SV

CH

SV maximum 

setting

-

+

40~ 120

35

Limit the maximum set temperature of SV

Press the "          " and "           " keys simultaneously for about 10 seconds, set (LCK=112), enter the engineering parameter group

A

Abnormal heating 
protection

OFF/ON

OFF

OFF: Turn this feature off, ON: Turn this feature on.

t

Continuous 
heating time

0~99M

20 MINS

Relay output synchronous timing time value

4.Control parameter description:

1. Description of operation interface: This instrument is composed of two 
parts: 
“temperature control” and “over-temperature protection”. The control 
parameters can be configured independently. Dual temperature probe 
temperature measurement ensures accurate temperature measurement. 
Dual high power relays ensure tempera-ture control and safe operation. The 
upper window is over-temperature protection, the lower window is 
temperature control, so the over-temperature SV value is more reasonable 
than the temperature-controlled SV value of about 2°C.

For example: When you want to control the water temperature inside thebox 
constant at 28 °C, you can set the following temperature control SV value is 
28 °C, the above over-temperature SV value is set to 30 °C. Whenthe 
temperaturerises to 28°C, the temperature control relay will cut off the outlet 
voltage output. If the voltage cannot be cut off (the temperature control part 
fails), when the temperature rises to 30°C, the over-temperature relay will 
also cut off the power supply of the outlet to prevent dangerous heating. In 
order to play a dual temperature protection

2.Heating operation description: After power-on, when PV<SV, the OUT 
indicator flashes slowly and the controller warms up. When the 
temperaturerises to SV-PV 

3°C, the OUT lamp starts flashing. When 

PV=SV, the controller turns off the output and the system stops heating. 
When the temperature drops to PV SV-bd, the OUT light flashes and the 
controller resumes heating operation. In order to achieve a constant 
temperature, work in this cycle.

3. temperature probe self-test failure: When the PV window shows "LLL" or 
"HHH" that is the temperature probe failure, you need to replace the same 
type of temperature probe can be.

4, over-temperature alarm function: When the control temperature exceeds 
the AL value,the PV window displays "EH" and other characters at the same 
time the buzzer sounds,the controller automatically shuts down the heating 
operation. At this point, the user should check the cause of the alarm, 
eliminate the fault and then run the power.

5. Abnormal heating protection function: After starting this protection 
function, when the temperature controller is heating. If the PV rise 
temperature is  3°C after continuous heating for "t” time, the heating 
system is considered to be abnormal and the PV window flashes “EP” fault 
code and beeps, and the output is turned off. Only power off can release the 
fault locked state. The customer can start this function if he is familiar with 
the characteristics of his heating system, otherwise it may cause false 
alarms.

6. Water level protection function: When the water level switch is selected, it 
can realize the power-off function when there is water shortage or the water 
level is too low, so as to prevent dangerous heating. When the water level 
switch detects that the water level is too low or there is no water, the 
controller will turn off the heating output, at the same time the water level 
indicator will light up with the alarm beep, and the above PV window will 
display the "ES" fault code. When the water level returns to normal, the 
alarm is released and normal temperature control operation resumes.

≤ 

1. Only when LCK=12 or 112 is set, press and hold 
the “            ” key for about 2 seconds to enter the 
parameter group to view or modify the parameter 
values.

2. When setting parameters, press “            ” or “           ” to
 modify the value. If there is no key operation for 10 
consecutive seconds, the modified data is automatically
 saved, exiting the setting state and returning to the 
normal operating state.

3. When changing the parameter value, press and hold
 the “        ” key to quickly increase the value.