Fail-Safe Operation

The XPander I/O Unit can be used in fail-safe* operation where relay outputs are reset to 

the non-active state on the event of internal battery pack failure or loss of radio communi-

cation. 

 *

Note - Requires compatible control panel software

The eighth segment is used to select normal (OFF) or fail-safe (ON) relay operation.

OUTPUT 2

OUTPUT 1

3V DC

SET

RST

INPUT 1 INPUT 2

LED

ENABLE

PO

WER

INPUT 

1

INPUT 

2

FAULT

CLOSED

0

1

1

64

F-SAFE

© Apollo Fire Detectors Limited/2009-10/TP

FIXING POSITION 1

FIXING POSITION 2

FIXING POSITION 3

FIXING POSITION 4

POWER JUMPER

TAMPER

RECOMMENDED

CABLE ENTRY POINTS

RECOMMENDED

CABLE ENTRY POINTS

3V DC

SET

RST

N/O

COM

N/C

N/O

COM

N/C

Address Setting

The address of the XPander I/O Unit is set using the first seven segments of the DIL switch. 

Each segment of the switch must be set to “0” (ON) or “1” (OFF), using a small screwdriver or 

similar tool. A complete list of address settings is shown below.

 

 

DIL switch  

 

DIL switch 

 

DIL switch 

 

DIL switch 

 

DIL switch

  setting 

 setting 

  setting 

 setting 

 setting

 

addr 1234567 addr 1234567 addr  1234567 addr 1234567 addr 1234567

 1 1000000  11 1101000  21  1010100  31 1111100  41 1001010

 2 0100000  12 0011000  22  0110100  32 0000010  42 0101010

 3 1100000  13 1011000  23  1110100  33 1000010  43 1101010

 4 0010000  14 0111000  24  0001100  34 0100010  44 0011010

 5 1010000  15 1111000  25  1001100  35 1100010  45 1011010

 6 0110000  16 0000100  26  0101100  36 0010010  46 0111010

 7 1110000  17 1000100  27  1101100  37 1010010  47 1111010

 8 0001000  18 0100100  28  0011100  38 0110010  48 0000110

 9 1001000  19 1100100  29  1011100  39 1110010  49 1000110

 

10 0101000  20 0010100  30  0111100  40 0001010  50 0100110

 

51 1100110  61 1011110  71  1110001  81 1000101  91 1101101

 

52 0010110  62 0111110  72  0001001  82 0100101  92 0011101

 

53 1010110  63 1111110  73  1001001  83 1100101  93 1011101

 

54 0110110  64 0000001  74  0101001  84 0010101  94 0111101

 

55 1110110  65 1000001  75  1101001  85 1010101  95 1111101

 

56 0001110  66 0100001  76  0011001  86 0110101  96 0000011

 

57 1001110  67 1100001  77  1011001  87 1110101  97 1000011

 

58 0101110  68 0010001  78  0111001  88 0001101  98 0100011

 

59 1101110  69 1010001  79  1111001  89 1001101  99 1100011

 

60 0011110  70 0110001  80  0000101  90 0101101  100 0010011

 

101 1010011  106 0101011  111  1111011  116 0010111  121 1001111

 

102 0110011  107 1101011  112  0000111  117 1010111  122 0101111

 

103 1110011  108 0011011  113  1000111  118 0110111  123 1101111

 

104 0001011  109 1011011  114  0100111  119 1110111  124 0011111

 

105 1001011  110 0111011  115  1100111  120 0001111  125 1011111

   

  

   

  

126 0111111

Fig 2

 - Wiring details

Fig 1

 - XPander I/O enclosure

INPUT

IP –

IP +

N/O

INPUT

CONTACT

20k
EOL

4k7

OUTPUT 1

© Apollo Fire Detectors Limited/2009-10/TB

N/O

COM

N/C

Wiring

Connect the input wiring as shown in Fig 2. The relay output may be used to switch up to 2A 

at 30V DC. The mains voltages must not be connected.

Note: Dual I/O shown, single I/O has input 2 and output 2 terminals and LEDs omitted