background image

XPander Input/Output Unit

Installation Guide

General

Do not install any XPander equipment until a full site survey has been completed using the 

XPander site survey tool. A maximum of 5 interfaces are permitted for each site. For sites 

that require more than 5 interfaces please contact Apollo. All installation engineers must 

have had certified XPander training.

The XPander Input/Output (I/O) Unit variants are available under the following part 

numbers:

Part Number

Description

XPA-IN-14011-APO

Single Input/Output Unit

XPA-IN-14012-APO

Dual Input/Output Unit

The installation must conform to BS5839-1:2008 (or applicable local codes). The XPander I/O 

Unit is suitable for indoor use only.

Compatibility

The XPander I/O Unit requires interface to be version 4B or higher.

Installation of XPander I/O Unit

Ensure that the XPander I/O Unit is sited in accordance with the survey and design require-

ments. The recommended minimum distance to any electrical equipment is two metres 

radius (three dimensionally).

1.  Calculate the number of cable entries and drill holes for cable glands in the lower 

portion of the enclosure accordingly (Fig 1). Remove and replace the PCB if necessary 

using anti-static precautions to avoid damaging the electronics.

2.  Mount the XPander I/O enclosure using suitable fixings (No. 6/3.5mm screw clearance, 

see Fig 1 for fixing positions) and connect all wiring. 

3.  Set the address and mode of relay operation; normal or fail safe (see address setting 

overleaf)

4.  Fit the power jumper shorting link and commission the unit according to the XPander 

commissioning guide PP2286.

LED Indication

In order to aid with commissioning, the XPander I/O unit has LED indication of input and 

output status. By default, LED indication is disabled to preserve battery life. LED indication 

is enabled by pressing the LED Enable button once. LED indication will remain active for 

10-minutes unless the button is pressed again.

 

  Relay on 

Illuminated red when relay is energised

 

  Switch Closed  Illuminated red when monitored field contact activated

 

  Fault 

Illuminated yellow when input wiring is open or short circuit

© Apollo Fire Detectors Limited 2009-2010

Apollo Fire Detectors Limited, 36 Brookside Road, Havant, Hampshire, PO9 1JR, UK

Tel: +44 (0) 23 9249 2412   Fax: +44 (0) 23 9249 2754

 Email: [email protected]   Website: www.apollo-fire.co.uk

1

PP2367/2010/Issue 2

Battery Type

6x AA, 1.5V Alkaline Duracell Procell (MN1500, LR6)

When replacing batteries, allow the device to power down for a period of two minutes 

before installing replacements.

Note: When replacement batteries are required, all batteries must be replaced together.

Technical Data

Operating voltage 

2.8-5VDC

Operating temperature 

–10°C to +50°C 

Relay rating 

2A at 30V DC

Switch closed resistance 

4K7Ω

End-of-line resistor 

20KΩ

 

Functional Testing

The interface and associated devices should be commissioned according to the commis-

sioning guide; PP2286.