When operated under XP95 or Discovery Protocols, EN54-13 type 2 devices
can be connected. In case EN54-13 type 1 devices need to be connected
they must be installed directly next to this module, with no transmission path
according to EN 54-13.
© Apollo Fire Detectors Limited 2016
Apollo Fire Detectors Limited, 36 Brookside Road, Havant, Hampshire,
PO9 1JR, UK
Tel: +44 (0) 23 9249 2412 Fax: +44 (0) 23 9249 2754
Email: techsalesemails@apollo- re.com Website: www.apollo- re.co.uk
Troubleshooting
Before investigating individual units for faults, it is important to check that
the system wiring is fault free. Earth faults on data loops or interface zone
wiring may cause communication errors. Many fault conditions are the
result of simple wiring errors. Check all connections to the unit.
LED Status Indicator
Commissioning
The installation must conform to BS5839–1 (or applicable local codes).
Caution
Unit damage. No electrical supply greater than 50V ac rms or 75V dc
should be connected to any terminal of this Switch Monitor.
Problem Possible Cause
No response or missing
Incorrect address setting
Incorrect loop wiring
Fault condition reported
Incorrect input wiring
Incorrect end-of-line resistor tted
Analogue value unstable
Dual address
Loop data fault, data corruption
Constant alarm or pre-alarm
Incorrect wiring
Incorrect end-of-line resistor tted
Isolator LED on
Short-circuit on loop wiring
Wiring reverse polarity
Too many devices between isolators
POLL/
ISO
Flashing Green
Device Polled
Continuous Yellow
Isolator Active
IP
Continuous Red
Input Active
Continuous Yellow
Input Fault
Note:
Not all LEDs can be
on simultaneously.
Fig. 1 Standard resistive monitoring mode
Fig. 2 Normally open monitoring mode (compatible with CoreProtocol only)
Fig. 3 Normally closed monitoring mode (Compatible with CoreProtocol only)
Address Setting
Examples
Connectivity
Examples
Mode
Description
1
DIL Switch XP Mode
2
Switch monitor - normal resistance bands with alarm delays
3
priority switch monitor - normal resistance bands
4
Switch monitor - N/C input with alarm delays
5
Priority switch monitor - N/C input
Mode Table*
*CoreProtocol enabled systems only