      When operated under XP95 or Discovery Protocols, EN54-13 type 2 devices 
      can be connected. In case EN54-13 type 1 devices need to be connected 
      they must be installed directly next to this module, with no transmission path 

      according to EN 54-13.

© Apollo Fire Detectors Limited 2016

Apollo Fire Detectors Limited, 36 Brookside Road, Havant, Hampshire, 

PO9 1JR, UK

Tel: +44 (0) 23 9249 2412   Fax: +44 (0) 23 9249 2754

 Email: techsalesemails@apollo-  re.com   Website: www.apollo-  re.co.uk

Troubleshooting

Before investigating individual units for faults, it is important to check that 

the system wiring is fault free. Earth faults on data loops or interface zone 

wiring may cause communication errors. Many fault conditions are the 

result of simple wiring errors. Check all connections to the unit.

LED Status Indicator

Commissioning

The installation must conform to BS5839–1 (or applicable local codes).

Caution

Unit damage. No electrical supply greater than 50V ac rms or 75V dc 

should be connected to any terminal of this Switch Monitor.

 

Problem  Possible Cause

 

No response or missing 

Incorrect address setting

 

 

Incorrect loop wiring

 

Fault condition reported 

Incorrect input wiring

 

 

Incorrect end-of-line resistor   tted

 

Analogue value unstable 

Dual address 

 

 

Loop data fault, data corruption 

  Constant alarm or pre-alarm 

Incorrect wiring

 

 

Incorrect end-of-line resistor   tted

 

Isolator LED on 

Short-circuit on loop wiring

 

 

Wiring reverse polarity

 

 

Too many devices between isolators

POLL/

ISO

Flashing Green

Device Polled

Continuous Yellow

Isolator Active

IP

Continuous Red 

Input Active

Continuous Yellow

Input Fault

Note:

Not all LEDs can be 

on simultaneously.

Fig. 1   Standard resistive monitoring mode

Fig. 2   Normally open monitoring mode (compatible with CoreProtocol only)

Fig. 3   Normally closed monitoring mode (Compatible with CoreProtocol only)

Address Setting

 Examples

Connectivity

 Examples

Mode

Description

1

DIL Switch XP Mode

2

Switch monitor - normal resistance bands with alarm delays

3

priority switch monitor - normal resistance bands

4

Switch monitor - N/C input with alarm delays

5

Priority switch monitor - N/C input

Mode Table*

*CoreProtocol enabled systems only 