39215-164/Issue 3
3
4
6
5
Addressing
Table 1
XP95 / Discovery Systems
CoreProtocol Systems
Se
g
m
e
n
t
1
Sets the address
Sets the address
2
3
4
5
6
7
8
Set to ‘0’ (Fault value is returned if set to ‘1’)
MCP
Priority interrupt - enables MCP behaviour
Enables 30 second delay into alarm
DLY
Enables 30 second delay into alarm
Enables priority enabled switch monitor behaviour
Note: On mixed systems addresses 127 and 128 are reserved. Refer to system’s panel manufacturer for
further information.
See Table 1
The 8th segment must be in set to ‘0’
for Discovery / XP95 operation
For connectivity instructions see Fig
1, 2 & 3
Intelligent DIN-Rail Switch Monitor
Installation Guide
Part No
Product Name
SA4700-300APO
Intelligent DIN-Rail Switch Monitor
Technical Information
All data is supplied subject to change without notice. Speci cations
are typical at 24V, 25°C and 50% RH unless otherwise stated.
Supply Voltage
Quiescent Current
Power-up Surge Current
LED Current
Maximum Loop Current
(I
c
max; L1 in/out)
Operating Temperature
Humidity
Approvals
17-35V dc
500µA
900µA
1.6mA per LED
1A
–40°C to 70°C
0% to 95% RH
(no condensation or icing)
EN 54-17 & EN 54-18
For additional technical information please refer to the following documents
which are available on request.
PP2563 - Intelligent DIN-Rail Switch Monitor