Apollo REACH WIRELESS RW1300-210APO Скачать руководство пользователя страница 3

PP5104/2022/Issue 1

Page 3 of 4

Maintenance and Service 

Maintenance must be performed in accordance with all 
applicable standards. Clean the detector externally using a 
soft damp cloth. For full cleaning and recalibration detectors 
should be returned to Apollo Fire Detectors.  

Batteries

REACH Wireless devices are supplied with two CR123 
batteries, battery A and B. The device switches periodically 
between the two batteries on a controlled sequence. For 
correct operation of the device, both batteries are required 
with adequate capacity reserves.

When battery A reaches a low power threshold, it will trigger 
a fault. This fault requires both batteries to be replaced in 
every instance as both batteries should be discharging 
equally.

When one (or both) batteries lack power, the Loop-Interface 
receives a low battery message and will signal this event on 
its in-built display, as well as relay the low battery message to 
the fire control panel. The battery fault will also be signalled 
by the device itself through its LED indicators if programmed 
(see table 1).

Tamper detection

REACH Wireless devices contain an anti-tamper mechanism. 
In the event of removal from its base, it sends a tamper 
detection message to the Loop-Interface.

Tampering detection is not signalled visually by the device 
LED.

EMC Directive 2014/30/EU 

REACH Wireless Sounder VAD Base complies with the 
essential requirements of the EMC Directive 2014/30/EU, 
provided that it is used as described in this datasheet. 

A copy of the Declaration of Conformity is available from 
Apollo on request. 

Construction Products Regulation (EU) 305/2011

The REACH Wireless Sounder VAD Base complies with 
the essential requirements of the Construction Products 
Regulation (EU) 305/2011 

A copy of the Declaration of Performance is available from 
Apollo on request.

Отзывы: