ORBIS

14

The TimeSaver Base® is a design 

that provides installers with an open 

working area with fixing holes shaped 

to allow a fast mounting procedure. 
The relay base incorporates a single-

pole voltage-free changeover contact 

for switching ancillary equipment. The 

maximum contact rating is 30V 1A.
When the detector changes to the 

alarm state, the relay is energised, 

causing the contact to change state. 

The contact will remain in this 

condition until the detector is reset.
A base is available which allows Orbis 

detectors to be used in ‘Sav-Wire’ 

detection and alarm systems. Care 

should be taken to connect Sav-Wire 

bases correctly as shown in fig 9.
The Orbis Heater base is designed 

to be used in cold climates where 

environmental conditions could 

result in either icing or condensation 

affecting the operation of detectors. It 

ORBIS

HEATER BASE

Part Number ORB-HB-00020-APO

ORBIS

TIMESAvER LX

Part Number ORB-MB-00002-APO 

ORBIS

ADAPTOR

Part Number ORB-BA-10008-APO 

LED 

COM —

IN +

OUT +

1

2

3

4

LED 

COM —

IN +

OUT +

1

2

3

4

+

_

To next 
detector

From 
control 
panel

Screen
(Functional 
Earth)

Screen
(Functional 
Earth)

COM

COM

N/C

N/C

N/O

N/O

RELAY

CONTROLLED 

DEVICE

RELAY

CONTROLLED 

DEVICE

TimeSaver relay base wiring connections

Figure 8

© Apollo Fire Detectors Limited 2004/JDR

EOL

Resistor

Remote

LED

From

Control

Panel

+

Screen

(Functional 

Earth)

© Apollo Fire Detectors Limited 2004/JDR 

COM   Not used
In +    Not used  
Out +  Not Used
LED -   Remote indicator

1  Remote ind
2  + Zone connection
3  - Zone connection
4  Earth screen

LED –

COM –

IN +

OUT +

1

2

3

4

LED –

COM –

IN +

OUT +

1

2

3

4

Sav-Wire base wiring connections

Figure 9

© Apollo Fire Detectors Limited 2004/JDR

NOTE: This Sav-Wire Base may be used only with compatible 

control panels.

ORBIS

RELAY BASE®

Part Number ORB-RB-10004-APO

ORBIS

SAv-WIRE BASE®

Part Number ORB-SW-10005-APO 

is recommended that the heater base 

be used in conjunction with either a 

Waterproof Base Cover or Deckhead 

Mounting Box to minimise moisture 

ingress.

An adaptor can be used to enable 

Orbis detectors to be fitted to Series 

60/65 bases.

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание ORB-HT-11001-APO

Страница 1: ...www apollo fire co uk ORBIS PRODUCT GUIDE Optical Detector Multisensor Detector Heat Detector Mounting Bases www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...ORBIS 2 conventional detectors from Apollo www acornfiresecurity com www acornfiresecurity com...

Страница 3: ...etectors work 11 Environmental performance 11 Technical Data 11 Orbis TimeSaver Base 12 Installing Orbis 12 Fitting Orbis detector heads 13 Orbis Features LED Status 13 TimeSaver LX 14 Relay Base 14 S...

Страница 4: ...f Orbis is to make installation commissioning and maintenance quicker enhance the reliability of detection and reduce the incidence of false alarms Orbis features TimeSaver Base designed for fast inst...

Страница 5: ...st which is an m value of 2 The performance of Orbis detectors is given as a solid line which shows how evenly the optical detectors respond to the test fires If detectors respond too quickly the lowe...

Страница 6: ...onfirmation of smoke before the alarm signal given The algorithms are used to verify signals from the sensing chamber to filter out transients and to decide when the detector should change to the alar...

Страница 7: ...LED 1 2k connected to negative supply characteristic MECHANICAL Material Detector and base moulded in white polycarbonate Alarm Indicator Integral indicator with 360 visibility See Table 3 on page 13...

Страница 8: ...ms The multisensor smoke detector has two sensors one for smoke one for heat and the alarm decision is derived from either sensor or a combination of both The multisensor is a development of the Orbis...

Страница 9: ...ts 40mA Alarm load 600 Holding voltage 5 33V Minimum holding current 8mA Minimum voltage to light 5V alarm LED Alarm reset voltage 1V Alarm reset time 1 second Remote output LED 1 2k connected to nega...

Страница 10: ...es heat detectors according to the highest ambient temperature in which they can safely be used without risk of false alarm The classes are identified by the letters A to G Class A is subdivided into...

Страница 11: ...acteristics and the choice of the right type for a particular application may not always seem straightforward It is helpful to understand the way that heat detectors are classified as explained earlie...

Страница 12: ...many installations bases with diodes are specified in order that an active end of line device may be fitted Diode bases are marked OD Loop continuity testing is facilitated as there is a continuity d...

Страница 13: ...ors are wired in the correct polarity Flashes once per second No Flash FasTest Maintenance procedure takes just 4 seconds to functionally test and confirm detectors are functioning correctly Flashes o...

Страница 14: ...Number ORB BA 10008 APO LED COM IN O U T 1 2 3 4 LED COM IN O U T 1 2 3 4 _ To next detector From control panel Screen Functional Earth Screen Functional Earth COM COM N C N C N O N O RELAY CONTROLLED...

Страница 15: ...pplied to the detector If this is the case the LED will flash red once a second StartUp will not check whether the IN and OUT connections have been transposed This is not a problem if standard bases a...

Страница 16: ...PP2147 2010 Issue 4 Apollo Fire Detectors Ltd 2003 2010 www acornfiresecurity com www acornfiresecurity com...

Отзывы: