CONVENTIONAL DETECTORS

In the case of heat detectors a fast test is 

defined as a sample which recognises a 

rise of 10°C within one minute.  Since 

sampling takes place every 2 seconds an 

Orbis heat detector will respond within 

about 4 seconds.
Smoke or Heat Testing
Smoke or heat testing Orbis detectors is 

aided by the FasTest® feature. A detector 

will react rapidly to the correct stimulus if 

applied within 4 minutes after power up. 
Choose the appropriate test function on 

the control panel and reset the detector 

circuit. This should place the detectors 

into FasTest®. Apply smoke or heat as 

appropriate and the detector should 

enter the alarm state within 4 seconds. 

The panel may sound the alarm and reset 

the zone automatically (refer to control 

panel’s instructions).  If not, silence the 

alarm and reset the panel. Repeat the 

procedure as necessary. 
Note that the multisensor detector will 

respond to either smoke or heat while 

in FasTest®. 

MAINTENANCE AND 

SERVICING 

Detectors should be checked regularly 

at the intervals indicated by the locally 

applicable code of practice. Apollo 

recommends that detectors be checked 

at least once a year.
One of the features of Orbis is FasTest® 

which makes it possible to carry out 

a functional test, using smoke or heat, 

within about four seconds. If detectors 

appear not to be functioning correctly 

they should be returned to Apollo for 

testing.
If detectors are externally dirty they 

can be cleaned carefully with a damp 

cloth using a small amount of industrial 

alcohol.
DirtAlert™
Orbis detectors have drift compensation 

to compensate for changes caused by the 

environment. The most usual change is 

contamination.
If the detector is dirty to the point where 

it can no longer compensate, its LED 

will flash yellow while it is in StartUp. 

Maintenance checks should therefore 

include removing a detector from its base 

and re-inserting it or pressing reset on the 

panel to initate StartUp. 

COMMMISSIONING 

MADE EASY 

Orbis has been designed with a number 

of features that make commissioning 

easier and that save time.
StartUp
When Orbis detectors are powered up 

they automatically enter a phase known 

as StartUp and in which they stay for 4 

minutes. After this they revert to normal 

operation.  If the detector is reset, ie, if 

power is disconnected for one second 

or longer, the detector  will always enter 

StartUp for the first four minutes after 

power has been restored. The detector 

LED flashes red once a second to indicate 

that it is in StartUp.
What StartUp indicates
StartUp is used to check that the positive 

and negative cables are connected in the 

correct polarity and that power has been 

applied to the detector. If this is the case, 

the LED will flash red once a second.
StartUp will not check whether the IN+ 

and OUT+  connections have been 

transposed. This is not a problem if 

standard bases are used as the detector 

will operate normally.
If, however, diode bases are used and 

a detector is removed from a base with 

transposed positive connections none 

of the detectors beyond this point will 

operate. 
FasTest®
Orbis detectors incorporate a test facility 

known as FasTest®.
In normal operation Orbis smoke 

detectors do not change to the alarm 

state at the first sensing of smoke.   If 

they did, they could be too sensitive and 

cause false alarms. Algorithms determine 

the point at which the detector changes 

to alarm.
This could slow down routine 

maintenance during which detectors are 

tested by means of smoke or a smoke-

simulating substance.
In order to avoid such a problem Orbis 

detectors have FasTest, a facility which 

is automatically available during StartUp 

and which modifies algorithms so that 

testing is possible within 4 seconds.
The problem of testing is even more 

acute in the case of heat detectors as they 

absorb a great deal of heat during testing. 

Orbis heat detectors also incorporate 

FasTest®.

A flashing yellow LED is not a sign 

that the detector needs to be replaced 

immediately. The decision to replace 

should be taken by the service engineer, 

taking the environment of the detector into 

account. If the detector is not replaced it 

will evenually cause false alarms.
When deciding how long to leave the 

detector on site in such a case, the 

following rule of thumb may be used:
 installation time + 25%
For example, if a detector had been 

installed for four years when the LED 

flashed yellow, it could be left in place 

for up to 12 months.
Dirty detectors can be returned to Apollo 

for cleaning and recalibration. 

APPROVALS AND 

REGULATORY 

COMPLIANCE 

The Orbis range of detectors is approved 

by a large number of certification bodies.  

These include approvals to EN54:200 

with LPCB, Vds, DIBT, BOSEC and FG.  

For further information on approvals held 

by Apollo contact the Sales Department 

or visit our website (details on page 2).

EU DIRECTIVES

Orbis complies with the requirements of 

a number of European New Approach 

Directives such as the EMC Directives 

2004/108/EC and the Construction 

Products Directive 89/106/EEC.  Visit 

the Apollo website to download EC 

certificates of conformity issued by 

the Notified Body, LPCB.  Copies of 

Declarations of Conformity issued by 

Apollo for all applicable New Approach 

Directives are available on the Apollo 

website or from Apollo on request.
All Orbis products comply with the 

marking requirements of the WEEE 

Directive,  2002/96/EC.    For  further        

information on disposing of applicable 

electrical and electronic waste contact 

Apollo.

Содержание ORB-BA-10008-APO

Страница 1: ...www apollo fire co uk ORBIS PRODUCT GUIDE Optical Detector Multisensor Detector Heat Detector Mounting Bases ...

Страница 2: ...ractive CONTACT POINTS FOR ENQUIRIES AND HELP Technical queries techsales apollo fire co uk Resources literature photos marketing apollo fire co uk Sales enquires sales apollo fire co uk Phone number for all departments 44 0 23 9249 2412 Fax for all departments 44 0 23 9249 2754 Website www apollo fire co uk and compact design means that Orbis will blend in well with all architectural styles Orbis...

Страница 3: ...ctor 10 How do Orbis heat detectors work 11 Environmental performance 11 Technical Data 11 Orbis TimeSaver Base 12 Installing Orbis 12 Fitting Orbis detector heads 13 Orbis Features LED Status 13 TimeSaver LX 14 Relay Base 14 Sav Wire Base 14 Heater Base 14 Orbis Adaptor 14 Commissioning made easy 14 StartUp 15 What StartUp indicates 15 FasTest 15 Smoke or Heat Testing 15 Maintenance and Servicing...

Страница 4: ...nd electronic The purpose of Orbis is to make installation commissioning and maintenance quicker enhance the reliability of detection and reduce the incidence of false alarms Orbis features TimeSaver Base designed for fast installation StartUp for fast commissioning FasTest reduces maintenance time automatic drift compensation with DirtAlert warning to easily identify dirty detectors SensAlert whi...

Страница 5: ...espond before the end of test which is an m value of 2 The performance of Orbis detectors is given as a solid line which shows how evenly the optical detectors respond to the test fires If detectors respond too quickly the lower shaded portion of the graph they may be too sensitive and hence likely to generate false alarms If detectors respond too slowly the upper shaded portion they are in danger...

Страница 6: ...nges in sensitivity extra confirmation of smoke before the alarm signal given The algorithms are used to verify signals from the sensing chamber to filter out transients and to decide when the detector should change to the alarm state All this combines to increase detection reliability and reduce false alarms HOW DOES THE ORBIS OPTICALDETECTORWORK Orbis operates on the well established light scatt...

Страница 7: ...time 1 second Remote output LED 1 2kΩ connected to negative supply characteristic MECHANICAL Material Detector and base moulded in white polycarbonate Alarm Indicator Integral indicator with 360 visibility See Table 3 on page 13 for details of flash rate Dimensions 97mm diameter x 31mm height 100mm diameter x 46mm height in base Weight Detector 75g Detector in base 135g ENVIRONMENTAL Temperature O...

Страница 8: ...high immunity to false alarms The multisensor smoke detector has two sensors one for smoke one for heat and the alarm decision is derived from either sensor or a combination of both The multisensor is a development of the Orbis optical detector described in the previous chapter and goes further in its capabilities of fire detection The optical sensor is identical to the one in the Orbis optical de...

Страница 9: ...At 12 volts 20mA At 24 volts 40mA Alarm load 600Ω Holding voltage 5 33V Minimum holding current 8mA Minimum voltage to light 5V alarm LED Alarm reset voltage 1V Alarm reset time 1 second Remote output LED 1 2kΩ connected to negative supply characteristic MECHANICAL Material Detector and base moulded in white polycarbonate Alarm Indicator Integral indicator with 360 visibility See Table 3 on page 1...

Страница 10: ...andard EN54 5 2001 classifies heat detectors according to the highest ambient temperature in which they can safely be used without risk of false alarm The classes are identified by the letters A to G Class A is subdivided into A1 and A2 In addition to the basic classification detectors may be identified by a suffix to show that they are rate of rise suffix R or fixed temperature suffix S types All...

Страница 11: ... wide range of response characteristics and the choice of the right type for a particular application may not always seem straightforward It is helpful to understand the way that heat detectors are classified as explained earlier and to memorise a simple rule use the most sensitive heat detector available consistent with avoiding false alarms In the case of heat detectors it may be necessary to ta...

Страница 12: ...ll switch the remote LED In many installations bases with diodes are specified in order that an active end of line device may be fitted Diode bases are marked OD Loop continuity testing is facilitated as there is a continuity device in the base The continuity device enables power to pass through every base in a loop to ensure that each is connected correctly Once a detector is fitted to the base t...

Страница 13: ...Up Confirms that the detectors are wired in the correct polarity Flashes once per second No Flash FasTest Maintenance procedure takes just 4 seconds to functionally test and confirm detectors are functioning correctly Flashes once per second No Flash DirtAlert Shows that the drift compensation limit has been reached No Flash Flashes once per second in StartUp Stops flashing when StartUp finishes S...

Страница 14: ...002 APO ORBIS ADAPTOR Part Number ORB BA 10008 APO LED COM IN O U T 1 2 3 4 LED COM IN O U T 1 2 3 4 _ To next detector From control panel Screen Functional Earth Screen Functional Earth COM COM N C N C N O N O RELAY CONTROLLED DEVICE RELAY CONTROLLED DEVICE TimeSaver relay base wiring connections Figure 8 Apollo Fire Detectors Limited 2004 JDR EOL Resistor Remote LED From Control Panel Screen Fun...

Страница 15: ...y and that power has been applied to the detector If this is the case the LED will flash red once a second StartUp will not check whether the IN and OUT connections have been transposed This is not a problem if standard bases are used as the detector will operate normally If however diode bases are used and a detector is removed from a base with transposed positive connections none of the detector...

Страница 16: ...PP2147 2010 Issue 4 Apollo Fire Detectors Ltd 2003 2010 ...

Отзывы: