Apollo 51000-600 Скачать руководство пользователя страница 13

 

 

WARNING: IMPORTANT INFORMATION FOR THE USER 

Individuals with medical problems may consider using warning devices which 

provide audible and visual signals for carbon monoxide concentrations under 30 
ppm. 

 

WARNING

 

Actuation of your CO alarm indicates the presence of carbon monoxide (CO) 

which can KILL YOU. 

If alarm signal sounds: 

1. Operate reset/silence button. 

2. Call your emergency services (fire department or 911). 
3. Immediately move to fresh air - outdoors or by an open door/window. Do a 

head count to check that all persons are accounted for. Do not reenter the 

premises nor move away from the open door/window until the emergency 

services responders have arrived, the premises have been aired out, and 

your alarm remains in its normal condition. 

4. After following steps 1 - 3, if your alarm reactivates within a 24 hour 
period, repeat steps 1 - 3 and call a qualified appliance technician (Telephone 

Number) to investigate for sources of CO from fuel burning equipment and 

appliances, and inspect for proper operation of this equipment. If problems 

are identified during this inspection have the equipment serviced 

immediately. Note any combustion equipment not inspected by the 

technician and consult the manufacturers' instructions, or contact the 

manufacturers directly, for more information about CO safety and this 
equipment. Make sure that motor vehicles are not, and have not been, 

operating in an attached garage or adjacent to the residence. 

The premises should be well ventilated when household cleaning supplies or 

similar contaminants are used. 

DETECTOR REPLACEMENT 

This detector is manufactured with a long-life carbon monoxide sensor. Over time 
the sensor may lose sensitivity and may need to be replaced with a new carbon 

monoxide detector. The 

detector’s lifespan is 

10 years from the date of 

manufacture. 

NOTE: 

When the detector is removed from its base, a tamper message is sent to the 

central station. 

The detector will also cause a trouble condition once it has reached the end of its 
useful life. If this occurs, it is time to replace the detector. 

NOTE: 

Before replacing the detector, notify the proper authorities that 

maintenance is being performed and the system will be temporarily out of service. 

Disable the zone or system undergoing maintenance to prevent any unwanted 

alarms. Dispose of the detector in accordance with any local regulations. 

NOTE: 

The replacement date that appears on the device is the date beyond which 

the device may no longer detect carbon monoxide accurately and should be 

immediately replaced.

 

 

CAUTION 

It should be noted the installation, operation, testing and maintenance of a carbon 

monoxide detector is different to smoke detectors. Per NFPA 720 section 5.3.7.2 a 
CO detector shall not be connected to a zone that signals a fire condition (i.e. smoke 

detectors zones). Therefore, the carbon monoxide alarm signal must be 

programmed as a non-fire zone. 

See the control’s 

installation instructions for the 

appropriate carbon monoxide zone type to be programmed. 

13.

 

SPECIFICATIONS 

 

Transmitter Frequency: 345.000 MHz (crystal controlled) 

 

Dimensions: Ø 5’’ x 2.

7

5’’ high (Ø

 125mm x 70mm high) 

 

Weight (including battery): 10.5 oz (300 g) 

 

Color: White 

 

Audible Signal (ANSI Temporal 3/Temporal 4): 85dBA min. in alarm (at 10ft / 

3m)

 

 

Sensitivity: 2.00 

 3.34%/foot obscuration

 

 

Operating Temperature: 40°F to 100°F (4.4°C to 37.8°C)

  

 

Operating Humidity: 15%-90% RH Non-Condensing

 

 

Supplementary heat rating: 135°F  

 

Supplementary heat spacing rating: 70ft

 

Содержание 51000-600

Страница 1: ...ransmitter sends a signal to the control panel The Wireless Combination Smoke Heat and Carbon Monoxide Detector contains an integrated fixed 41 F 5 C temperature freeze sensor that will send a warning signal based on temperature detected This detector is designed to provide protection with 70 foot spacing capability The detector can send alarm tamper and battery condition messages to the system s ...

Страница 2: ...Figure 1 Detector Front 2 2 DETECTOR BACK Figure 2 Detector Back CO Test Button Indicator LEDs Fire Test Button CO Sensor Gas Entry Port Anti Tamper Lock Release Sounder Tamper Switch Mechanism Anti Tamper Lock Mechanism Battery Compartment ...

Страница 3: ...dication for the detector operating modes and states In general RED is used to indicate ALARM conditions YELLOW is used to indicate FAULT conditions and GREEN is used for normal operation see Detector Status LED Sounder operating modes table 4 1 DETECTOR STATUS LED SOUNDER OPERATING MODES Status Description LEDs Sounder Smoke Alarm Smoke has been detected 3 RED flashes in time with sounder Tempora...

Страница 4: ...tector has been removed from the base 1 YELLOW flash followed by 1 GREEN flash every 12 seconds None Power Up The detector has had batteries installed and is powered up 1 RED flash followed by 1 YELLOW flash followed by 1 GREEN flash A single chirp Normal Operation The detector is operating normally with no fault or alarm conditions 1 GREEN flash every 12 seconds None Table 1 Detector Status LED S...

Страница 5: ...d in Section 9 FIELD SERVICE TESTS of this installation guide WARNING CONSTANT EXPOSURES TO HIGH OR LOW TEMPERATURES OR HIGH HUMIDITY MAY REDUCE BATTERY LIFE 6 PROGRAMMING TO CONTROL PANEL Refer to the appropriate compatible control panel programming guide for the proper procedure required to enroll the Wireless Combination Smoke Heat and Carbon Monoxide Detector into the system 7 MOUNTING THE DET...

Страница 6: ...he ceiling surface and begins to bank down from the ceiling The corner where the ceiling and wall meet is an air space into which the smoke could have difficulty penetrating In most fires this dead air space measures about 0 1m 4in along the ceiling from the corner and about 0 1m 4in down the wall Detectors should not be placed in this dead air space see Figure 9 Figure 10 and Figure 11 Where NOT ...

Страница 7: ...it level arrangement Figure 9 Example of proper mounting for detectors Figure 10 Example of proper mounting for detectors with sloped ceilings Figure 11 Example of proper mounting for detectors with peaked ceilings ...

Страница 8: ...cked damaged or inadvertently removed 7 3 MOUNTING PROCEDURE NOTE The Wireless Combination Smoke Heat and Carbon Monoxide Detector should only be installed by a competent technician or installer NOTE The Wireless Combination Smoke Heat and Carbon Monoxide Detector must not be used with a guard NOTE DO NOT attach the detector to removable ceiling panels NOTE Two warning labels are provided with the...

Страница 9: ...moved from the mounting base The detector also includes an anti tamper feature which prevents the detector being removed from the mounting base To enable the anti tamper feature cut the anti tamper tab on the mounting base Figure 16 and Figure 17 and install the detector on the mounting base When the anti tamper feature has been enabled to remove the detector from the mounting base a small screwdr...

Страница 10: ...l sound Temporal 3 and the LED will blink RED along with the sounder Continue to press and hold the fire test button for up to 12 seconds to ensure the smoke alarm signal is sent to the control panel Verify the signal was received at the control panel 9 3 SMOKE ALARM FUNCTIONAL TEST Using SDi SOLO A10 SDi Smoke Centurion or SDi Smoke Sabre canned smoke products according to the labeled instruction...

Страница 11: ...ecting about half of the occupants in potentially fatal fires Victims are often intimate with the fire too old or too young or physically or mentally impaired such that they cannot escape even when warned early enough that escape should be possible For these people other strategies such as protection in place or assisted escape or rescue would be necessary A battery powered alarm must have a batte...

Страница 12: ...el burning appliances including appropriate ventilation and exhaust systems Carbon monoxide gas is a highly poisonous gas which is released when fuels are burned It is invisible has no smell and is therefore impossible to detect with the human senses Under normal conditions in a room where fuel burning appliances are well maintained and correctly ventilated the amount of carbon monoxide released i...

Страница 13: ... monoxide sensor Over time the sensor may lose sensitivity and may need to be replaced with a new carbon monoxide detector The detector s lifespan is 10 years from the date of manufacture NOTE When the detector is removed from its base a tamper message is sent to the central station The detector will also cause a trouble condition once it has reached the end of its useful life If this occurs it is...

Страница 14: ...t installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interfer...

Отзывы: