background image

APD0671 A160301

© 2016 Apollo Fire

 Copyright © 2016 l 

1

51000-300

WIRELESS SMOKE ALARM INTERCONNECT BASE

GENERAL INFORMATION

The Wireless Smoke Alarm Interconnect Base part number 51000-300 is a 120V AC 

powered sensor. It monitors the interconnect line on interconnected hardwired smoke 

alarm systems and sends out a transmission when any of the smoke alarm units on the 

same circuit enter an alarm state. The device has LEDs to visually indicate the status of the 

interconnect base. A single CR2032 ba� ery provides backup power in the event that AC 

power is lost on the alarm system circuit. The Wireless Smoke Alarm Interconnect Base 

communicates with a compa� ble control panel and can send alarm, low ba� ery, AC power 

loss, and supervisory messages to the system's receiver.

Contents of Carton:

• 1  � Wireless Smoke Alarm Interconnect Base

• 2  �  2" long 10-32 Screws

• 1  �  CR 2032 3 Volt Coin Ba� ery

Figure 1. 51000-300 Kit

IMPORTANT: This device must be tested and maintained regularly. This device is intended 

for use with compa� ble smoke alarms, but will not detect the presence of smoke, heat, or 

 re directly.

 

Note: Each of the smoke alarms part of interconnected smoke alarms must be:

• Present in every required loca� on per NFPA 72,11.5.1

• Con rmed as less than ten years from date of installa� on (or manufacture). Please 

check label on the device or original smoke detector device manual.

• Hardwired to a single, common 120V AC circuit designated for interconnected smoke 

alarms.

• Pass the manufacturer's stated tes� ng regimen to con rm proper interconnect 

opera� on.

• Have fresh back-up ba� eries.

• On the list of compa� ble models (any model not listed may work but has not been 

compa� bility tested).

• This device shall not be installed in loca� ons where the normal ambient temperature 

is below 40F(4.4C) or exceeds 100F (37.8C), unless the alarm has been determined 

capable of being used at installa� on points with higher or lower ambient temperatures.

• Please see sec� on at the end regarding informa� on on the proper installa� on of smoke 

alarms that are intended to work with the Wireless Smoke Alarm Interconnect Base.

This device is not intended to work with smoke alarms paired with smoke alarm guards, 

unless the combina� on has been evaluated and found suitable for this purpose.

Compatible Smoke Alarm Models

• BRK Brands Model 7010B: AC Powered Photoelectric Smoke Alarm with Ba� ery 

Backup

• Firex Kidde Model i4618: Hardwire Ioniza� on Smoke Detector with Ba� ery Backup

• First Alert BRK Model 9120B: Hardwired Smoke Alarm with Ba� ery Backup

• Kidde Model i12040: 120V AC Wire-in Smoke Alarm with Ba� ery Backup

• USI Electric Model 5304: Hardwired Ioniza� on Smoke and Fire Alarm with Ba� ery 

Backup

CAUTION:  Before a� emp� ng  installa� on, locate the primary electrical circuit that 

powers the interconnected hardwired smoke alarm system and shut off  or disconnect 

power to this circuit. An electrical shock hazard is present if this electrical circuit is not 

temporarily disabled during installa� on.

AVERTISSEMENT: Avant de commencer l’installa� on, trouver le circuit électrique 

principal qui alimente le système câblé de détec� on de fumée interconnecté 

et l’éteindre ou couper l’alimenta� on de ce circuit. Un risque d’électrocu� on 

est présent si ce circuit électrique n’est pas temporairement coupé pendant 

l’installa� on.  

WARNING: Remember to turn on or reconnect power to the primary electrical circuit 

that powers the interconnected hardwired smoke alarm system. The  re warning system 

may be disabled if electrical power is not restored to the system.

ATTENTION : Ne pas oublier d’établir ou de rétablir le courant du circuit électrique 

principal qui alimente le système câblé de détec� on de fumée interconnecté. Le 

système d’alerte incendie serait inopérant si le courant électrique alimentant le 

système n’était pas rétabli.

Install Wireless Interconnect Base

Select a smoke alarm that will be used to provide power and communicate to the 

wireless interconnect base. Any smoke alarm that is within range of a compa� ble 

wireless receiver can be selected if the smoke alarm is part of an interconnected 

hardwired system.

Remove the exis� ng smoke alarm from the exis� ng  moun� ng bracket. This is 

usually done by twis� ng the alarm counter clockwise or clockwise from where it 

is mounted.

Figure 2. Remove Exis� ng Smoke Alarm from Smoke Alarm Moun� ng Base

Figure 3. Unplug Pigtail of Exis� ng Smoke Alarm

Unplug the exis� ng smoke alarm from the smoke alarm pigtail. Loosen the two screws 

used to hold the exis� ng moun� ng bracket and remove it from the wall or ceiling.

Figure 4. Remove Exis� ng Smoke Alarm Moun� ng Bracket from Wall or Ceiling

Figure 5. Install Wireless Smoke Alarm Interconnect Base between Wall and 

Moun� ng Bracket

Place the interconnect base where the exis� ng moun� ng bracket was located. Make 

sure the wire/wiretaps are inserted through the center opening of the smoke alarm 

moun� ng bracket.

Place the exis� ng smoke alarm moun� ng bracket on top of interconnect base.  Align the 

interconnect base and the smoke alarm moun� ng bracket and replace the two screws 

used to hold the bracket in place. Tighten all screws down.

 

NOTE: It is suggested that the smoke alarm sensor LEDs be oriented towards the 

bo� om or in a manner that allows the LEDs on the unit to be visible.

Figure 6. Wiretaps/Wires, & Pigtail through Center 

PRINTER’S INSTRUCTIONS:

INSTR,INSTL,APOLLO WIRELESS SMKE ALARM INTERCONNECT BASE - P/N: 10011636 X1- INK: BLACK - MATERIAL: 20 LB. MEAD BOND - SIZE: 8.500” X 11.000” - TOL. +/- .125”- SCALE: 1-1 -  FOLDING: FOLD 1X TO FINAL SIZE: 8.500" X 5.500"- FINISH WITH LOGO 

SHOWING

+

CR2032

3V

WIRELESS SMOKE ALARM
INTERCONNECT BASE

WIRETAPS

CR2032
COIN BATTERY

10-32 X 2” 
SCREWS

SMOKE

EXISTING 
SMOKE
ALARM
MOUNTING 
BASE 

EXISTING 
SMOKE
ALARM

ROTATE
COUNTER
CLOCKWISE
TO REMOVE

EXISTING SMOKE
ALARM

EXISTING SMOKE ALARM
MOUNTING BRACKET

UNPLUG
SMOKE ALARM
FROM EXISTING 
POWER PIGTAIL

REMOVE EXISTING SMOKE
ALARM MOUNTING 
BRACKET FROM WALL OR
CEILING

EXISTING
SMOKE
ALARM
POWER
PIGTAIL

ACCESS HOLE
IN WALL OR 
CEILING

REMOVE
EXISTING
SCREWS

WIRELESS SMOKE 
ALARM INTERCONNECT
BASE

EXISTING SMOKE ALARM
MOUNTING BRACKET

EXISTING
POWER
PIGTAIL

WALL ACCESS HOLE

WIRETAPS (3)
(NOT CONNECTED)

WIRELESS SMOKE
ALARM INTERCONNECT
BASE

EXISTING 
SMOKE 
ALARM 
MOUNTING
BRACKET

EXISTING 
POWER
PIGTAIL

WIRETAPS (3)
(NOT CONNECTED)

MOUNT BRACKET
WITH LED’S AT BOTTOM

Apollo

WIRELESS SMOKE ALARM INTERCONNECT BASE

MODEL 51000-300

Содержание 51000-300

Страница 1: ...n trouver le circuit électrique principal qui alimente le système câblé de détec on de fumée interconnecté et l éteindre ou couper l alimenta on de ce circuit Un risque d électrocu on est présent si ce circuit électrique n est pas temporairement coupé pendant l installa on WARNING Remember to turn on or reconnect power to the primary electrical circuit thatpowerstheinterconnectedhardwiredsmokealar...

Страница 2: ... to slide the ba ery tray out of the device Remove the ba ery from the tray and replace with a new CR2032A ba ery Slide the ba ery tray back into the unit making sure that the tray is fully inserted into the unit NOTE Use Panasonic CR2032A ba eries or equivalent Use of another ba ery may damageornega velyaffecttheopera onofthedevice End of Life TheWirelessSmokeAlarmInterconnectBasedoesnothaveanEnd ...

Страница 3: ...e or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help To satisfy FCC IC RF exposure safety requirements a separation distance of 20 cm or more sh...

Страница 4: ...APD0671 A160301 2016 Apollo Fire 25 Corporate Drive Auburn Hills Michigan 48326 1 248 332 3900 FAX 1 248 332 8807 www apollo fire com SalesUSA apollo fire com ...

Отзывы: