Apator Powogaz INVONIC H Скачать руководство пользователя страница 13

 

- 13 -

 

2018-05-09

 

Power supply for the Modbus/BACnet module 

 

Voltage:

 

12-24 V DC 

 

Typical supply current:

 

50 mA 

 

Maximum power consumption:

 

2 W 

 

Terminal numbering:

 

60 and 61 (bipolar connection) 

 

Communication interface 

 

Modbus protocol type:

 

RTU 

 

BACnet protocol type:

 

MS/TP (ANSI/ASHRAE standard 135, version 1, revision 9; ISO 16484-5) 

 

Modbus data transmission baud rate:

 

1200, 2400, 4800, 9600, 19200, 38400, 56000, 57600, 115200 

 

BACnet data transmission baud rate:

 

9600, 19200, 38400, 57600, 115200 

 

Available data formats:

 

8E1, 8O1, 8N2 

 

Terminal numbering:

 

90 (+), 91 (-) 

5.2.6.  Installation of the external power supply module 

Module installation procedure: 

1. 

Remove the installer's security seals from the calculator enclosure. 

2. 

Open the calculator's lid by releasing the black latches on the left and right-hand side of the enclosure. 

3. 

Install the module in place of the second battery holder (see Fig. 5.6.)

4. 

Fix the board of the module to the calculator body with one fixing screw supplied with the module 

5. 

Disconnect the connector plug of the battery installed in the meter from the battery connector and connect it directly to the module (see Fig. 

5.6.)

6. 

Use a metal tool to short-circuit (for 1-2 seconds) both pins of the battery connector which you have just disconnected from the battery 

connector plug. This will unload the internal capacity of the meter bus. 

7. 

Connect power connector plug of module to the meter's battery connector. The LCD display should start indicating. 

8. 

By means of pliers remove the protective cap from the spare sealant hole in the bottom part of calculator enclosure. 

9. 

Insert the power cable (use a flexible two-wired cable 0.14-0.5 mm

2

, with outer diameter 4-6 mm) in sealant hole and route the cable through 

an available cable fittings and make a strain relief protecting wire against being pulled out from the outside (see Fig. 10.3.). 

10. 

Connect wires of the power cable to the screw terminals of external power supply module (bipolar connection). Full terminal assignment of 

the external power supply module, see Table 10.3. 

11. 

Install the configuration pin connector jumper in the test mode (see Fig. 6.7). 

12. 

Use an optical interface to connect with the optical interface port on the meter's calculator front panel. Press the button on the calculator 

front panel and connect with the meter with a dedicated service software suite to set the date and time (Current Readings tab) and disable 

the M-Bus data communication limit (Meter Configuration tab). 

13. 

Remove the configuration pin jumper to disable the test mode and restore the normal operating mode of the heat and cooling meter. 

14. 

Close the lid of the calculator, secure the side clasps of the calculator enclosure, and install the installer's security seals in place. 

15. 

Connect the power cable to the external power supply source. The green LED on the calculator front panel should be on – this indicates 

that the meter runs on external power. 

 

 

Fig. 5.6. Installation of external power supply module in the meter’s calculator. 

The external power supply module provides possibility of powering meter with 12-42 V DC 12-36 V AC 50/60 Hz,10 mA max. When device is 

power supplied from an external source, the meter does not use the internal battery power. The internal battery power in such case is used only 

to keep the meter running when the external power supply source is turned off. 

The external power supply module can be powered by e.g. the optional 230 V 50/60 Hz / 12 V AC power adapter (see Fig. 5.7.). If you want to 

use it, connect the grey cable of the power adapter to the external power supply module terminals by passing it through a cable gland of the 

calculator, and connect the black cable marked with label (230 V AC) to the 230 V 50/60Hz power mains. As the power adapter is powered by 

Содержание INVONIC H

Страница 1: ...z S A ul Klemensa Janickiego 23 25 60 542 Pozna Poland tel 48 61 84 18 101 fax 48 61 84 70 192 www apator com Ultrasonic heat and cooling meter INVONIC H Installation operating manual ISO 9001 PN N 18...

Страница 2: ...g 14 5 3 1 Mounting of calculator 14 5 3 2 Mounting of flow sensor 15 5 3 3 Mounting of temperature sensors 16 5 4 Setting up the jumper 16 5 5 Verifying the installation and configuration 17 5 6 Seal...

Страница 3: ...guaranteed by proper insulation of electrical wiring leak proof connections of the flow sensor and temperature sensors on the service pipeline reliable fitting of the meter components in the service i...

Страница 4: ...ion type and size Code 0 6 m3 h 110 mm threaded DN15 G A 0 6 m3 h 190 mm threaded DN20 G1 B 0 6 m3 h 190 mm flanged DN20 C 1 m3 h 110 mm threaded DN15 G D 1 m3 h 190 mm threaded DN20 G1 E 1 m3 h 190 m...

Страница 5: ...me from pulse input 1 and 2 energy and volume of last month with write date energy and volume of last year with write date active errors with timestamp operating time without energy calculation error...

Страница 6: ...0 DN65 25 0 50 0 0 250 0 050 300 20 0 DN65 40 0 80 0 0 160 0 080 300 18 0 DN80 40 0 80 0 0 400 0 080 300 18 0 DN80 60 0 120 0 0 240 0 120 360 18 0 DN100 60 0 120 0 0 600 0 120 360 18 0 DN100 Working m...

Страница 7: ...m flow rate value measurement date 11 Maximum working medium supply temperature measurement date 12 Maximum working medium return temperature measurement date 13 Minimum working medium supply temperat...

Страница 8: ...equipped with external power supply module 12 42 V DC or 12 36 V AC 50 60 Hz 10 mA max The power supply module is installed inside the calculator in place designated for second battery In such case me...

Страница 9: ...V1 2 hT2 hT1 Q1 0 The meter s calculator provides all the necessary measurement and data storage functions 4 Marking and sealing 4 1 Marking 4 1 1 Calculator There are following information on the fro...

Страница 10: ...technical documentation of other system components and in meter installation project Do not place the meter s wiring cables less than 5 cm away from power cables of other equipment Do not change leng...

Страница 11: ...module into designated contact socket see Fig 5 3 The contact pins of module must not be bent 4 Fix the board of the module to the calculator body with two fixing screws supplied with the module 5 In...

Страница 12: ...in p 5 2 6 concerning Installation of the external power supply module 7 Close the lid of the calculator fasten the latches on the sides of the calculator enclosure and mount again the installer s sec...

Страница 13: ...ing wire against being pulled out from the outside see Fig 10 3 10 Connect wires of the power cable to the screw terminals of external power supply module bipolar connection Full terminal assignment o...

Страница 14: ...several different ways Installation of the calculator directly on the flow sensor enclosure with possibility to rotate calculator 180 or 90 if special bracket is used Note it is possible to install th...

Страница 15: ...rectly on a wall if there is a risk of humidity condensation on the wall or the wall surface temperature might fall below 5 C In such case it is recommended to install calculator with a minimum gap of...

Страница 16: ...or rinse the pipeline well mounting spacer instead of flow sensor for the time of flushing Proper performance of the meter requires that the pipeline was pressurized completely filled with the working...

Страница 17: ...he meter must be sealed once it has been installed as explained in p 4 2 to prevent unauthorized dismantle removal or altering the device without evident damage on the meter or its seals Installer s s...

Страница 18: ...se LCD indicates error code screen 1 1 6 3 Menu structure 6 3 1 Viewing the readings in normal mode user s menu The menu structure in a normal operating mode is presented in Fig 6 3 Fig 6 3 Viewing th...

Страница 19: ...g energy 1 6 Total volume of working medium 1 7 Total volume from 1st pulse input Displayed only when pulse input 1 has been previously activated in the meter by the software 1 8 Total volume from 2nd...

Страница 20: ...revious billing year and date stamp Displayed only when pulse input 1 has been previously activated in the meter by the software 2 7 Volume from 2nd pulse input in previous billing year and date stamp...

Страница 21: ...previously activated in the meter by the software 2 14 Volume from 2nd pulse input in previous billing month and date stamp Displayed only when pulse input 2 has been previously activated in the meter...

Страница 22: ...medium on supply and return pipe in previous billing month and date stamp 2 24 2 583 Data from the past months with the date stamp up to last 36 months By analogy to 2 8 to 2 23 With the service softw...

Страница 23: ...of the temperature supply or return or temperature difference 3 12 Tariff 2 settings As in menu 3 11 only L1 change to L2 See parameter 3 11 notes 3 13 1st pulse input output configuration Input inpu...

Страница 24: ...tware version number 3 19 Serial number of meter 3 20 Primary M Bus address 3 21 Meter operating time in hours without energy calculation error 3 22 Battery operation time in hours Note The values of...

Страница 25: ...ulation of nominal flow During test value of nominal flow is constantly displayed After the test the energy and volume of the working medium are stored in the memory until the next simulation is start...

Страница 26: ...pond to sum of errors 8 4 2 1 In a case when value of at least one digit of error code is 8 the thermal energy calculation and summation of the working medium volume and operation time without errors...

Страница 27: ...r from the configuration pin connector disables the test mode and restores the normal mode Once the test mode has been disabled the meter displays previously recorded integral parameter values 6 5 Rem...

Страница 28: ...tel 48 61 84 18 101 fax 48 61 84 70 192 10 Appendix A Fig 10 1 Electrical wiring diagram T1 supply temperature sensor T2 return temperature sensor V1 pulse input output 1 V2 pulse input output 2 Fig 1...

Страница 29: ...T 1 energy value output in the test mode Table 10 2 Numbering of the screw terminals for the optional communication modules Terminal no Destination 20 current loop module 21 current loop module 24 25...

Страница 30: ...IC H meter s calculator dimensions INVONIC H meter dimensions Fig 11 2 Flow sensor qp 0 6 1 0 1 5 m3 h Fig 11 3 Flow sensor qp 1 5 2 5 m3 h G threaded connection G1 threaded connection installation le...

Страница 31: ...5 2 5 m3 h Fig 11 5 Flow sensor qp 0 6 1 0 1 5 2 5 m3 h G1 threaded connection DN20 flanged connection installation length L 190 mm installation length L 190 mm Fig 11 6 Flow sensor qp 3 5 6 0 m3 h G1...

Страница 32: ...2018 05 09 32 Fig 11 7 Flow sensor qp 3 5 6 0 m3 h DN25 flanged connection installation length L 260 mm Fig 11 8 Flow sensor qp 10 0 m3 h G2 threaded connection installation length L 300 mm...

Страница 33: ...2018 05 09 Fig 11 9 Flow sensor qp 10 0 m3 h DN40 flanged connection two flange types installation length L 300 mm Fig 11 10 Flow sensor qp 15 0 m3 h DN50 flanged connection installation length L 270...

Страница 34: ...25 0 m3 h DN65 flanged connection installation length L 300 mm Fig 11 12 Flow sensor qp 40 0 m3 h DN80 flanged connection installation length L 300 mm Fig 11 13 Flow sensor qp 60 0 m3 h DN100 flanged...

Страница 35: ...12 2 Sealing the flow sensor qp 0 6 1 1 5 2 5 m3 h Fig 12 3 Sealing the flow sensor qp 3 5 6 m3 h threaded flanged connection threaded flanged connection installation length L 110 mm 130 mm 190 mm in...

Страница 36: ...type with permanently connected signal leads Fig 12 7 Sealing the directly mounted temperature sensors DS and DL type Environmental protection Do not dispose of with regular waste trash Take the prod...

Отзывы: