8
[UP]
and
[DOWN]
(at the same time): input in the parameter configuration menu (after
hold time longer than 1 s). If parameter 49:
PPro
=
on
(password protection is activated)
enter the access code (chapter 10)
[F]
: activation of a function programmed with parameter 50:
Func
(after holding for more
than 1 second, chapters 9.1 and 10)
b) button functions in the parameter configuration menu and the quick access menu (chapters 10 and 11)
Button
Description
[and marking in the contents of the instructions]
[SET]
:
- selection of the item displayed in the configuration menu (entering a lower level)
- edits the current parameter (the value blinks in the lower display)
- approves and saves the edited parameter value
[UP]
or
[DOWN]
:
- moves to the next or previous parameter (submenu)
- changes the value of the edited parameter
or
[UP]
and
[DOWN]
(simultaneously) or
[F]
:
- returns to the previous menu (higher level)
- cancels changes to the edited value (the blinking stops)
- returns to the measurement display mode (only
[UP]
and
[DOWN]
after hold time >0.5 s)
c) functions of the LED signaling diodes
Diode
[marking]
Description
[1] [2] [3]
signals switching on of outputs P1/SSR1, P2/SSR2, and P3/SSR3
9.1. FUNCTION BUTTON
The
[F]
function button starts the function that is programmed with parameter 50:
Func
(chapter 10). Activation or
deactivation of the function is indicated by appropriate messages on the lower display (described below).
Available functions of the
[F]
button
Source Description (
depending on the value of parameter 50:
Func
)
Message
Func
=
nonE
[F]
button is inactive (factory setting)
-
Func
=
Set3
step-wise change of the set value for the P1/SSR1 output
(day = parameter 20:
Set1
/night = 30:
Set3
, Table 10)
Set1
/
Set3
Func
=
bLoc
keyboard lock (with the exception of button
[F]
)
bLoc
/
boFF
Func
=
hAn1
unconditional manual mode for the P1/SSR1 output (chapter 12.8)
hAnd
/
hoFF
Func
=
hAn2
unconditional manual mode for the P2/SSR2 output
hAnd
/
hoFF
Func
=
hAn3
unconditional manual mode for the P3/SSR3 output
hAnd
/
hoFF
Func
=
hAnA
unconditional manual mode for the analog output
hAnd
/
hoFF
Func
=
StSP
control start/stop (applies to all outputs)
Star
/
StoP
Func
=
inpu
unconditional view of the measured values from inputs 1 and 2
inoF
/
inpu