ALM
LINK
Brown: 24VL
Blue: 0VL
B281SB-02U –
Brown: 24VL
Black: OUT
B281PB-02U –
Brown: 24VL
Blue: 0VL
B281SB-02US –
Brown: 24VL
Black: IN
Blue: 0VL
Brown: 24VL
Black: OUT
B281XB-02U –
Brown: 24VL
Black: IN
Blue: 0VL
Black: OUT
Blue: 0VL
B281XB-02US –
Black: OUT
Blue: 0VL
B281PB-02US –
-B281*B02U*CC20 9/17-
Address setting
Parameter setting
Address setting
■
Common procedure for address writer operation
[Various Settings]
Connect this unit to the AnyWireASLINK master unit.
Perform the setting using the address writer with the
transmission signal (DP, DN) supplied.
An address number is set as a beginning number from which part of the transmission frame is occupied to the terminal.
Set the address number within the range of bit address “0 to 254.”
(For the input/output mixed type, the same address number should be assigned to both input and output.
Make sure that the above wires are not
short-circuited during transmission signal
is connected.
Short-circuit may cause a fault of the
equipment.
Black: DN
Red: DP
*
For the power supply to be connected, be sure to use a
24V DC stabilized power supply.
CAUTION
AnyWireASLINK
master
24V DC
*
Transmission
signal
Lot No. 19ECBNB
- Set the address number so that the area occupied by the terminal does not exceed the transmission points of the master unit.
- Make sure that the address number setting is not duplicated.
- Also, use the address writer to read an address number that has been written in the terminal.
The factory-set address is “bit address 255” or “bit address 511,” which indicates that an address
has not been set.
The factory-set address varies depending on lot No., as follows:
For S/W version “B” or later version: Bit address 511
For S/W version “A” or 3-digit lot No.: Bit address 255
Input and output operations are disabled with the factory-set address.
S/W version
CAUTION
Example:
Be sure to connect to the AnyWireASLINK master unit to use.
An address writer ARW-04 (Ver. 04-1.01 or later version) or ARW-03 (Ver. 2.10 or later
version) is required for operation.
For the details of the operating method, refer to the product guide of the address writer.