Switch settings
3-1
3. Switch settings
3.1 Node address setting switch
Set the node address on the DeviceNet side by using the node address setting switch.
Do not change the node address while the unit is in operation.
The range in which the node address can be set varies depending on the master to be used.
If another node is already using the selected address, a node address redundancy will occur and the
address cannot start communication.
Node address
Node address setting switch
x10
x1
0
0
0
1
0
1
2
0
2
・
62
6
2
63
6
3
3.2 Transmission point number setting switch
Set the number of transmission points for the AnyWireASLINK.
This setting also changes the number of bytes occupied by the DeviceNet.
SW
Number of transmission points
DeviceNet occupied byte
number
1
2
Input
Output
Total
Input
Output
ON
ON
32 points
32 points
64 points
16
16
OFF
ON
64 points
64 points
128 points
20
20
ON
OFF
128 points
128 points
256 points
28
28
OFF
OFF
256 points
256 points
512 points
44
44
* Always turn off the power before changing the DIP switch settings.
3.3 SET switch
This is a switch for performing error flag clear, and slave automatic address recognition.
(1) Error flag clear
Pressing the SET switch clears the error flag.
This is the same operation as clearing the error flag of the output memory.
P5-7
(2) Automatic address recognition
Pressing the SET switch for approximately two seconds or more lights up the
“SET” LED to start
automatic address recognition.
P6-1