Anybus Configuration Manager (MAPS)
18 (56)
5.3.2
BACnet Server
This section contains settings related to BACnet communication.
Fig. 11
BACnet configuration
General Configuration
Device Name
The BACnet
Device Name
property. Can be modified here and/or from BACnet.
Device Instance
The BACnet
Device Object Instance
property for this device. This is a unique ID
for the BACnet device inside a single BACnet network segment.
Password
A password may be required to allow some BACnet commands. If not required or
unsure, leave as default (admin).
Gateway Mode
Mode
Select BACnet/IP or BACnet MSTP communication.
BACnet/IP settings:
UDP Port
The UDP port to use for BACnet. Default = 47808 (BAC0 in hex notation)
Network Role
If you are not familiar with BACnet it is recommended to leave this to
Disabled
.
•
Disabled
: The gateway will not provide any special service regarding
network communication and settings.
•
Foreign Device
: The gateway will act as a foreign device from the BACnet
network point of view.
•
BBMD
: The gateway will act as a BBMD on the BACnet network.
BACnet MSTP settings:
Max. Masters
The maximum number of supported BACnet MSTP masters.
Max. Info Frames
The maximum number of Info frames.
Baudrate
The BACnet MSTP communication speed.
MAC Address
The BACnet MSTP MAC address for the gateway.
Modbus to BACnet Gateway User Manual
SCM-1202-049 1.0