Operating Manual ECD3AM-00-00
Page 1 of 13
(07/16) R0117AGB
Operating Manual
Retrofit Speed-Controller Type
ECD3AM-00-00
Replacement for
ECdrive Type D400B001, Ziehl-Abegg
Страница 1: ...Operating Manual ECD3AM 00 00 Page 1 of 13 07 16 R0117AGB Operating Manual Retrofit Speed Controller Type ECD3AM 00 00 Replacement for ECdrive Type D400B001 Ziehl Abegg...
Страница 2: ...LECTRICAL INSTALLATION 6 3 3 INFORMATION ON EMC 7 3 4 ELECTRICAL CONNECTION CONTROLLER 8 3 5 OPERATING AND DISPLAY ELEMENTS 9 3 6 ADJUSTMENT 9 3 7 ADJUSTMENTS INTERNAL 10 3 8 CODING JUMPERS INTERNALLY...
Страница 3: ...thoroughly Ensure that the voltage is less than 60V before touching electrical contacts The user must use independent monitoring units in order to ensure that a malfunctioning drive is stopped safely...
Страница 4: ...0 90 UZK Max output current IMmax 6 5 A Phase Continuous output current IM 3 A Phase Rated output power 1 SN 0 9 kVA Efficiency ca 95 Power loss idling2 PV0 ca 18 W Power loss full load PV ca 50 W Ma...
Страница 5: ...Operating Manual ECD3AM 00 00 Page 5 of 13 07 16 R0117AGB 2 2 Dimensions...
Страница 6: ...tricity The discharging can be achieved by touching a grounded metal surface beforehand Due to the leakage currents of the controller 3 5 mA via the protective conductor PE must be in accordance with...
Страница 7: ...nes are to be laid two way source and target large area and well conducting to a ground1 In case of poor potential equalization between shielded connections an additional balancing network of at least...
Страница 8: ...nes Motor 1 RLG U 2 RLG V 3 RLG W 4 Encoder active High n c 5 Encoder active Low 6 Supply voltage 7 Supply voltage 8 Shield X8 Connectors for signal lines 1 15 V 2 0 V 3 Com Opt out 4 Ready 5 Stand st...
Страница 9: ...N Controller ready OFF Controller collective fault Intermediate circuit 450 V Intermediate circuit 150 V Heat sink temperature 80 C If there is a fault the output stage is disabled immediately The fau...
Страница 10: ...the engine at standstill n n max Sollwert 10V 0V I max Internal factory setting may not be changed tH Ramp up time of the set point integrator tR Return time of the set point integrator Setting the s...
Страница 11: ...SET n max PI tH tR STB1 Jumper position a Brake A cut off of the control voltage on connecting terminal 2 5 and or X2 6 causes the motor to come to a standstill This is the normal operation mode of th...
Страница 12: ...STB1 S1 L2 UZK Rotation direction logic Set point intergator Drehzahlregelung monitoring heatsink temperature UZK switching power internal voltage supply counter clockwise clockwise Output stage enge...
Страница 13: ...hnical documentation the measures are described with which the drive regulator complies with the EMC limiting values The electromagnetic compatibility of the machine is based on the method and thoroug...