4. Read Status Operation
Viewing and Printing a Read Status
42
IQ-636X Operations Manual P/N 52181:A 04/28/2005
Viewing and Printing a Read Status
To view or print Read Status information follow the instructions below:
Note:
If attempting to read a point that is not installed, the control panel displays “Not Installed”.
During all Read Status operations (except print operations) the control panel starts a 2-minute timer
each time you press a key. If the control panel does not detect a key press for 2 minutes, the control
panel exits Read Status and returns to the “System Normal” display.
In Read Status, you can also do the following:
•
Press the
ESC
key to delete the previous entry.
•
Press the S
YSTEM
R
ESET
key to abort Read Status.
Option
Press
Lets you
Read Point
0
key,
ENTER
key
View information for a detector, module, NAC,
Panel Circuit, or zone
Print Points
1
key,
ENTER
key
Print information for all installed points in the
system
Read History
2
key,
ENTER
key
Display the total number of events in the History
buffer and step through each event in sequence
Print History
3
key,
ENTER
key
Print the contents of the History buffer (up to 800
events)
Read Alarm History
4
key,
ENTER
key
View a display of the number of alarms in the Alarm
History buffer, then scroll through each alarm event
Print Alarm History
5
key,
ENTER
key
Print the contents of the Alarm History buffer (up to
200 events)
Содержание AUTOPULSE IQ-636X
Страница 1: ...A P N 52181 A ECN 05 034 Document 52181 04 28 2005 Rev ...
Страница 8: ...8 IQ 636X Operations Manual P N 52181 A 04 28 2005 Notes ...
Страница 12: ...12 IQ 636X Operations Manual P N 52181 A 04 28 2005 Notes ...
Страница 14: ...14 IQ 636X Operations Manual P N 52181 A 04 28 2005 Notes ...
Страница 20: ...20 IQ 636X Operations Manual P N 52181 A 04 28 2005 Notes ...
Страница 40: ...40 IQ 636X Operations Manual P N 52181 A 04 28 2005 Notes ...
Страница 66: ...66 IQ 636X Operations Manual P N 52181 A 04 28 2005 Notes ...
Страница 84: ......