Programming
How to Enter Program Change
84
IQ-301 PN 50036:F 10/29/2001
How to Program a Panel Circuit
Panel circuit program functions and Type Codes are similar to control modules.
Because the four Panel Circuits are always installed, the autoprogram feature does not
display Panel Circuits. Figure 68 shows a sample edit screen for Panel Circuit point
programming:
Figure 68 Sample Panel Circuit Edit Screen
To edit a Panel Circuit point select the Type Code. To do so, move the cursor to the
Type Code field (the Type code field will blink when selected). Select a Type Code by
pressing the up key until your desired Type Code appears. Table 25 contains a list of
the Notification Appliance Circuits (NACs) Type Codes.
Table 25 contains Type Code selections for the four Notification Appliance Circuits:
Table 25 Notification Appliance Circuit Type Codes
How to Delete a Detector or Module Point
You can use the Delete Point option to temporarily delete an intelligent detector or
module point from program memory. Selecting option 2 from the Point Programming
screen (Figure 63) lets you choose a detector or module point to delete. Figure 69
shows the Delete Point Selection screen and contains instructions for accessing a point.
Type Code Label
Special Function
BELL
CIRCUIT
None (default)
STROBE
CKT
None
HORN
CIRCUIT
None
AUDIBLE
CKT
None
blank
Use when no other Type Code applies
RELEASE
CKT
Short = Normal (nonpower-limited, see Appendix D)
REL
CKT
ULC
Short = Trouble (supervised and power-limited, see
Appendix D)
PROGRM@BELL@CIRCUIT
PANEL@CIRCUIT@NO.@1
Z00@Z@@@@Z@@@Z@@@Z
@@@@@@@@@@@@SW@BO1
“B” (bell circuit) in the address
Default zone selection
is Z00 (general alarm)
Walk Test (W) is selected by default.
(* = not selected). For details on Walk
Test, refer to “How to do a Walk Test
(6=walk test)” on page 99.
Type Code (For explanations,
refer to Table 25)
Custom label for
this device.
CBE selections
Two-digit address (01-04)
Silenceable (S) is selected by default.
(* = not selected).