System Overview
General Description
14
IQ-301 PN 50036:F 10/29/2001
Section 1 System Overview
1.1 General Description
The AUTOPULSE IQ-301 is a compact, cost-effective, intelligent fire alarm control
panel with an extensive list of powerful features. The power supply and all electronics
are contained on a single circuit board, providing a complete fire control system for
most applications. Optional modules which plug into the main circuit board are
available for special functions.
1.2 Features
Figure 1 identifies major features of the control panel.
•
Single standard communication
(SLC) loop, meets NFPA Style 4, 6,
or 7 requirements
•
198 intelligent device capacity
•
Four Notification Appliance Circuits
standard
•
Optional RTM-8 eight-zone relay
module with transmitter
•
Optional 411, 411UD, 411UDACT,
or 911AC Digital Alarm
Communicator/Transmitter
•
Optional UDACT Universal Digital
Alarm Communicator/Transmitter
•
LCD-80 liquid crystal display,
mounts up to 6,000 feet (1,828.8 m)
from panel
•
ACS annunciators, including LDM
custom graphic annunciators
•
ACM-8R remote relay module,
increases point capacity
•
Printer interface
•
Real time clock, with European
format option
•
History file with 650 event capacity
•
Intelligent features
•
Sensitivity display in percent
•
Manual sensitivity adjustment
•
Day/Night automatic sensitivity
adjustment
•
Drift compensation (U.S. patent
pending)
•
Auto detector test (meets NFPA 72)
•
Maintenance Alert
•
Pre-Alarm (AWACS™ — 2 levels)
•
LED blink control
•
Releasing features
•
Four independent hazards
•
Cross zone (three methods)
•
Delay timer
•
Soak timer
•
Abort — four options
•
Manual release
•
Waterflow (non-silenceable)
selection per module point
•
Supervisory selection per point with
separate LED
•
Alarm Verification
•
Walk Test
•
Positive alarm sequence (PAS)
pre-signal per NFPA 72
•
Silence Inhibit timer option
•
Auto silence timer option
•
March time/temporal code
•
Two-stage option for Canada
•
California code
•
Tornado warning code
•
Remote Ack/Silence/Reset/Drill via
Monitor Modules
•
Automatic time control functions,
with holiday exceptions
•
Autoprogram (learn mode) reduces
installation time
•
Password- and key-protected
nonvolatile memory.
•
Programmable from a PC with a
Windows®-based programming
utility
•
Rapid poll algorithm for manual
stations (U.S. patent pending)
•
Operates up to 1,000 feet (304.8 m)
with untwisted, unshielded wire
(U.S. Patent 5,210,523)
•
Operates sounder base on Action
Pre-Alarm level with general
evacuation on alarm level.
•
Burglar alarm point option.
•
Read status on program via modem
using dial-up phone lines.
•
Marine cabinet option (CAB-AM)