Calculating the System Current Draw
Power Supply Calculations
IQ-301 PN 50036:F 10/29/2001
129
Table 47 contains three columns for calculating current draws. For each column,
calculate the current and enter the total (in amps) in the bottom row. When finished,
copy the totals from Calculation Column 2 and Calculation Column 3 to Table 48 on
page 131.
Notes for Table 47:
1. Refer to the Notifier Device Compatibility Document for compatible devices and
their current draws.
2. For non-English language systems, the LCD-80TM (Terminal Mode) standby
current is 0.100 A.
3. Do not enter current for NAC #3 and NAC #4 in Table 47 if powering these circuits
from an AVPS-24 or APS-6R. For more information on the AVPS-24 and
APS-6R, refer to Appendix J.
4. The RTM-8 alarm current is based on all eight alarm relays being activated. The
alarm current can be reduced by 0.019 A for each zone (between zone 1 and
zone 8) that is not used by the system.
5. Enter in Column 2: “number of MMX-2 plus FZM-1” multipled by 0.090
Table 47 System Current Draw Calculations
(Part 1)
Row Category
Calculation Column 1
Primary, Non-Fire Alarm Current
(amps)
Calculation Column 2
Primary, Fire Alarm Current
(amps)
Calculation Column 3
Secondary, Non-Fire Alarm
Current (amps)
Qty
X [current draw]=
total
Qty
X [current draw]=
total
Qty
X [current draw]=
total
1
Basic System
N/A
N/A
N/A
N/A
N/A
N/A
1
x [0.10]
0.10
2
APS-6R
[ ]
x [0.025]=
3
AVPS-24
[ ]
x [0.009]=
4
High ripple power
TB1 terminals 1 and 2
Notification apps. via control module
Notification apps. via control module
Releasing devices via control module
Other compatible devices (Note 1)
N/A
N/A
N/A
[ ]
N/A
N/A
N/A
[ ]
N/A
N/A
N/A
[ ]
[ ]
[ ]
[ ]
[ ]
x [ ]=
x [ ]=
x [ ]=
x [ ]=
[ ]
[ ]
[ ]
[ ]
x [ ]=
x [ ]=
x [ ]=
x [ ]=
5
Non-resettable power
TB1 terminals 3 and 4
AFM-16AT/AFM-32A Series
ACM-16AT/ACM-32A Series
AEM-16AT/AEM-32A Series
AFM-16A
LCD-80, LCD-80TM (Note 2)
ACM-8R (refer to Doc. 15342)
LDM (refer to Doc. 15885)
UDACT Communicator
Other compatible devices (Note 1)
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
x [0.040]=
x [0.040]=
x [0.002]=
x [0.025]=
x [0.100]=
x [ ]=
x [ ]=
x [0.040]=
x [ ]=
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
x [0.056]=
x [0.056]=
x [0.018]=
x [0.065]=
x [0.100]=
x [ ]=
x [ ]=
x [0.100]=
x [ ]=
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
[ ]
x [0.040]=
x [0.040]=
x [0.002]=
x [0.025]=
x [0.050]=
x [ ]=
x [ ]=
x [0.040]=
x [ ]=
6
Resettable Power
Four-wire smoke detector
Two-wire smoke detector
connected to MMX-2/FZM-1 (Note 5)
A77-716B Relay
Other compatible devices (Note 1)
[ ]
[ ]
[ ]
[ ]
x [ ]=
x [ ]=
x [0.020]=
x [ ]=
[ ]
[ ]
[ ]
[ ]
x [ ]=
x [ ]=
x [0.020]=
x [ ]=
[ ]
[ ]
[ ]
[ ]
x [ ]=
x [ ]=
x [0.020]=
x [ ]=
7
NAC #1 (Note 1)
TB2 terminals 1 and 2
Notification Appliance
Releasing Solenoid
[ ]
[ ]
x [ ]=
x [ ]=
8
NAC #2 (Note 1)
TB2 terminals 3 and 4
Notification Appliance
Releasing Solenoid
[ ]
[ ]
x [ ]=
x [ ]=
9
NAC #3 (Notes 1 and 3)
TB2 terminals 5 and 6
Notification Appliance
Releasing Solenoid
[ ]
[ ]
x [ ]=
x [ ]=
10 NAC #4 (Notes 1 and 3)
TB2 terminals 7 and 8
Notification Appliance
Releasing Solenoid
[ ]
[ ]
x [ ]=
x [ ]=
Subtotals (carry to top line of Part 2)