Ansul AutoPulse Acclimate Plus FAPT-851 Скачать руководство пользователя страница 2

Installation

The FAPT-851 plug-in detector uses a separate base to
simplify installation, service, and maintenance. A special tool
allows maintenance personnel to plug-in and remove detec-
tors without using a ladder. Mount base on a box at least
1.5 in. (38 mm) deep. Suitable mounting base boxes include:

• 3.5 in. (89 mm) or 4.0 in. (102 mm) octagonal box

• Single-gang box (except relay or isolator base)

• With B224RB or B224BI base, use a 3.5 in. (89 mm)

octagonal box, or a 4.0 in. (102 mm) octagonal or square
box

Notes:

1) Because of the inherent supervision provided by

the SLC loop, end-of-line resistors are not required. Wiring
“T-taps” or branches are permitted for Style 4 (Class B)
wiring. 2) When using relay or sounder bases, consult data
sheet F-9587 (ISO-X) for device limitations between isolator
modules and isolator bases.

Application Note:

The FAPT-851 detector has the unique

ability to adjust sensitivity according to the environment,
based on heat and smoke levels. Avoid installing these
detectors in locations that are susceptible to rapid and high
temperature changes. An example of an incorrect application
would be near or in line with the output of a self-contained
heater.

Bases:

B210LP: . . . . . . . . . . . . 6.1 in. (155 mm) diameter
B501:. . . . . . . . . . . . . . 4.1 in. (104 mm) diameter
B200SR(A): . . . . . . . . . . . . . . . . Sounder Base
B224RB: .  .  .  .  .  6.2 in. dia. x 1.2 in. high (157 x 30 mm)

Relay type: . . . . . . . . . . . . . . . . . . . Form-C
Rating: . . . . . . . . . . . . 2.0 A @ 30 VDC resistive

0.3 A @ 110 VDC inductive

1.0 A @ 30 VDC inductive

Screw terminals: . . . . . . Up to 14 AWG (2.00 mm

2

)

B224BI Isolator: .  .  .  .  .  .  6.2 in. x 1.2 in. (157 x 30 mm)

Maximum: . . . . .  25 devices between isolator bases

Listings and Approvals*

UL . . . . . . . . . . . . . . . . . . . . . . . . . . . S1115
ULC . . . . . . . . . . . . . . . . . . . . . . . . . . S911**
Factory Mutual (FM) . . . . . . . . . . . . . . . . Approved
California State Fire Marshal (CSFM) .  .  .  .  7272-0028:206
MEA (NYC). . . . . . . . . . . . . . . . . . . . . 225-02-E
Maryland State Fire Marshal. . . . . . . . . . Permit #2122
UL Listed for In-Duct Applications

*Listings and Approvals are under NOTIFIER.

**System Sensor

Ordering Information

Shipping Weight

Part No. Description

lb

(kg)

432293

FAPT-851 Low-Profile

0.5

(0.23)

Smoke Detector

437078

FAPT-851A Low Profile

0.5

(0.23)

Smoke Detector (ULC)

438966

B210LP 6 in. (152 mm) Flanged 

1

(0.45)

Low Profile Base

417487

B501 European Flangeless Base

1

(0.45)

437438

B200SR Sounder Base

1

(0.45)

437439

B200SRA Sounder Base (ULC)

1

(0.45)

423945

B224RB Intelligent Relay Base

2

(0.9)

426125

B224BI Intelligent Isolator Base

2

(0.9)

417675

M02-04-00 Test Magnet

0.5

(0.23)

AUTO-
PULSE
IQ-318 OR
IQ-636X-2
CONTROL
PANEL

REMOTE ANNUNCIATOR

OPTIONAL RETURN LOOP

Address Dial on Back of Detector

Wiring Diagram (Standard Base)

006868

003582

LED 1

LED 2

MAGNET TEST
MARKER

PAINTED
SURFACE

PAINTED
SURFACE

TEST

MAGNET

TEST

MAGNET

004763

TEST MAGNET POSITIONING

TYCO FIRE PROTECTION PRODUCTS

Copyright © 2011  Tyco Fire Protection Products

ONE STANTON STREET

All rights reserved.

MARINETTE, WI 54143-2542

715-735-7411

Form No. T-2007121-3

FlashScan® is a registered trademark and Acclimate Plus™ are trademarks of Honeywell International.