8.    CONNECT THE DRAIN PIPE

Install the drainpipe of the indoor unit

The outlet has PTI screw bread, Please use sealing materials 

and pipe sheath(fitting) when connecting PVC pipes. 

The drain pipe of indoor unit must be heat insulated, or it will 

condense dew, as well as the connections of the indoor unit.

Hard PVC binder must be used for pipe connection, and make 

sure there is no leakage.

With the connection part to the indoor unit, please be noted not 

to impose pressure on the side of indoor unit pipes.

When the declivity of the drain pipe downwards is over 1/100, 

there should not be any winding.

The total length of  the drain pipe when pulled out traversely shall 

not exceed 20m, when the pipe is over long, a prop stand must 

be installed to prevent winding. 

Refer to the under figures for the installation of the pipes.

CAUTION

8.1

1.5m~2m

Insulating

material

Downward declivity

lower than 1/100 

Bend

S shape 

VP30

Downward declivity 

lower than 1/100

Put as deep as possible

(about 10cm)

Fig.8-1

70

100

60

80

Fig.8-2

Check the Leakage

7.3

Check all the joints with the leak detector or soap water. 

(See Fig.7-8 as a reference illustration)

NOTE

            In the figure

            A......Lo-stop valve

            B......Hi-stop valve

            C,D..Joints of the connecting pipe to the indoor unit.

B

A

D

C

Check-point of indoor unit

Check-point of outdoor unit

Fig.7-8

Additional Refrigerant Charge

7.2

CAUTION

Refrigerant cannot be charged until field wiring has been 

completed.

Refrigerant may only be charged after performing the leak test  

and the vacuum pumping.

When charging a system, care shall be taken that its maximum 

permissible charge is never exceeded, in view of the danger of 

liquid hammer.

Charging with an unsuitable substance may cause explosions 

and accidents, so always ensure that the appropriate 

refrigerant is charged.

Refrigerant containers shall be opened slowly.

Always use protective gloves and protect your eyes when 

charging refrigerant.

The outdoor unit is factory charged with refrigerant. 

Calculate the added refrigerant according  to the diameter  

and  the length  of  the  liquid side pipe of the outdoor 

unit/indoor unit connection.

NOTE:The number of bends is up to the length of the max 

height drop.Usually for each 10m need a bend. 

Table 7-4

Brass tube(mm)

R410A

R22

Ø6.35

Ø9.53

Ø12.7

Ø15.9

Ø19.0

0.022kg/m×(L-5)
0.011kg/m×(L-5)
0.060kg/m×(L-5)
0.030kg/m×(L-5)
0.110kg/m×(L-5)
0.060kg/m×(L-5)
0.170kg/m×(L-5)
0.085kg/m×(L-5)

0.250kg/m×(L-5)
0.125kg/m×(L-5)

0.030kg/m×(L-5)
0.015kg/m×L
0.065kg/m×(L-5)
0.030kg/m×L
0.115kg/m×(L-5)
0.060kg/m×L
0.190kg/m×(L-5)
0.095kg/m×L

0.290kg/m×(L-5)
0.145kg/m×L

orifice in the indoorunit  
orifice in the outdoorunit  

orifice in the outdoorunit  

orifice in the outdoorunit  

orifice in the outdoorunit  

orifice in the outdoorunit  

orifice in the indoorunit  

orifice in the indoorunit  

orifice in the indoorunit  

orifice in the indoorunit  

NOTE:the table above refer to the liquid tube.

Содержание Blue Star 12

Страница 1: ...laci n Thank you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference Conjunto Split Baja Silueta de Alta P...

Страница 2: ...as at least 3mm separation distance in all pole and a residual current device RCD with the rating of above 10mA shall be incorporated in the fixed wiring according to the national rule When carrying o...

Страница 3: ...drain piping in order to ensure proper drainage and insulate piping in order to prevent condensation Improper drain piping may result in water leakage and property damage Install the indoor and outdoo...

Страница 4: ...manual 6 Remote controller on some models 7 Frame on some models 9 Alkaline dry batteries AM4 2 1 11 Wire controller 1 1 1 1 2 1 2 Tubing Fittings Remote controller Its Frame Match with remote control...

Страница 5: ...the roof beam Strengthen the place that has been cut off and consolidatethe roof beam The installation of hanging screw bolts Fig 5 2 NOTE Confirm the minimum drain tilt is 1 100 or more Wooden constr...

Страница 6: ...rhang part Installing the dust proof net and canvas air passage 1 Install the dust proof net according to the installation manual 2 Install the canvas air passage underneath the dust proof net Diagram...

Страница 7: ...N 19 3 4 CONNECTING POINT OF DRAIN PIPE ELECTRICAL CONTROL BOX PLASTIC COVER 153 169 144 136 11 28 15 15 123 179 930 135 88 24 46 68 82 82 56 270 400 AIR OUTLET AIR INTAKE AIR INTAKE DUCT FLANGE 4 12...

Страница 8: ...wing method if the air conditioning s size of installationsite is limited and the indoor unit can t put into the installtionsite MODEL 24 36 Fig 5 11 For 24 36 Cooling Heating Air conditioner main bod...

Страница 9: ...ow in Fig 5 11 4 Clean the tray and evaporator 5 Re install the unit follow the reverse above orders 1 Please shut down the unit and cut off power cable before maintain the motor 2 Don t heavy pull th...

Страница 10: ...orders And connect the motor with electric control box as motor with power cable of capacity CAUTION 1 Please shut down the unit and cut off power cable before maintain the motor 2 Before dismount the...

Страница 11: ...tion of the arrow show in Fig 5 14 4 Clean the tray and evaporator 5 Re install the unit follow the reverse above orders 1 Please shut down the unit and cut off power cable before maintain the motor 2...

Страница 12: ...bolts from fan assembly see Fig 5 17 according to which orders to take off the fan assembly 3 Refer to Fig 5 17 horizontal pushing the fan assembly until it cannot not move any further and then lift...

Страница 13: ...peed 1300 1400 High speed Pa 190 100 1800 2000 2200 2400 1200 30K Low speed Mid speed External static pressure Pa 3 Air volume m h 1000 900 700 170 150 130 110 90 70 50 30 10 Slight speed 1400 1600 Hi...

Страница 14: ...oor unit The condensate should be well drained away by the drain hole to an appropriate place so as not to interfere other people Select the position where it will not be subject to snow drifts accumu...

Страница 15: ...4 895 590 333 355 302 862 313 990 624 366 396 340 966 354 990 624 366 396 340 966 354 990 624 366 396 340 966 354 990 624 366 396 340 966 354 360 940 600 376 400 340 1245 360 990 624 366 396 340 966 3...

Страница 16: ...ork To change air inlet is only necessary to interchange the indicated panels position Both panels use screws to be fixed to unit chassis Air inlet modification Change Panel Fig6 13 Table 6 3 30cm 30c...

Страница 17: ...ng in case of earthquake or strong wind Refer to Fig 6 15 To change air outlet is necessary to interchange panels too Fan outlet panel is attached to fan structure which must be mounted as follow Fig...

Страница 18: ...and its cover Bind the connecting pipe and the cables together tightly with binding tapes Pass the bound connecting pipe through the wall conduct from outside Be careful of the pipe allocation to do...

Страница 19: ...d fasten the nut 1 2 4 3 5 7 6 Using the vacuum pump 5 Fig 7 3 Remove the cap and turn the valve clockwise with the hexagon wrench Securely tighten the valve until the shaft contacts the main bodyseal...

Страница 20: ...Refrigerant Charge 7 2 CAUTION Refrigerant cannot be charged until field wiring has been completed Refrigerant may only be charged after performing the leak test and the vacuum pumping When charging a...

Страница 21: ...id a hazard The appliance shall be installed in accordance with national wiring regulations 4 3 5 6 7 10 WIRING CAUTION The appliance shall be installed in accordance with national wiring regualtions...

Страница 22: ...iring are correctly completed The refrigerant pipe system is leakage checked The drainage is unimpeded The heating insulation works well The ground wiring is connected correctly The length of the tubi...

Страница 23: ...ODEL POWER CIRCUIT BREAKER FUSE A PHASE FREQUENCY AND VOLT 18 24 60 30 36 42 48 208 240V 208 240V 1Phase 1Phase 208 240V 1Phase 208 240V 1Phase 208 240V 1Phase Table 10 3 Table 10 4 MODEL POWER CIRCUI...

Страница 24: ...60 42 60 380 420V 25 20 25 20 40 25 45 35 208 240V 3Phase 380 420V 3Phase 3Phase 208 240V 3Phase Table 10 5 Table 10 6 PHASE FREQUENCY AND VOLT POWER indoor POWER outdoor 30 20 30 20 40 30 40 35 50 40...

Страница 25: ...ong elec signal link wiring Weak elec signal link wiring Indoor Unit Outdoor Unit Ground the air conditioner properly in case to affect its anti interference function Ground wiring Ground wiring Power...

Страница 26: ...ioner properly in case to affect its anti interference function A disconnection device having an air gap contact separation in all active conductors should be incorporated in the fixed wiring accordin...

Отзывы: